Main
Associated head
ZCEH2
ZCE06
ZCE66
ZCE28
ZCE27
ZCE11
ZCE63
ZCE67
ZCE21
ZCE14
ZCE24
ZCE07
ZCE08
ZCE13
ZCE62
ZCE29
ZCE65
ZCE64
ZCE10
ZCEH0
ZCE02
ZCE01
ZCE05
Body type
Fixed
design
Compact
Device short name
ZCP
[ui] rated insulation voltage
300 V conforming to UL 508
500 V (pollution degree 3) conforming to IEC 60947-1
300 V conforming to CSA C22.2 No 14
Series name
Standard compact
Complementary
product compatibility
XCKP
Handle front plate colour
65 mm
Product or component type
Limit switch body
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
Associated connection component
ZCPEN12
ZCPEP20
ZCPEG11
ZCPEP16
ZCPEF12
ZCPEG13
Contacts insulation form
Zb
Contacts material
Silver plated contacts
contact operation
Slow-break, simultaneous
Contacts type and composition
2 NO
body material
Plastic
width (w)
31 mm
contact code designation
B300, AC-15 (Ue = 240 V), Ie = 1.5 A conforming to EN/IEC 60947-5-1 appendix A
R300, DC-13 (Ue = 250 V), Ie = 0.1 A conforming to EN/IEC 60947-5-1 appendix A
Net weight
0.07 kg
depth
30 mm
electrical durability
5000000 cycles, DC-13 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Positive opening
Without
electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Minimum actuation speed
6 m/s
Poles description
2
Short-circuit protection
10 A cartridge fuse, type gG
Environment
Ambient air temp for storage/transportation
-40…70 °C
Range of product
Telemecanique Limit switches XC Standard
ambient air temperature for operation
-25…70 °C