Main
Associated head
ZCE07
ZCE08
ZCE11
ZCE10
ZCE62
ZCE06
ZCE29
ZCE01
ZCEH2
ZCE02
ZCE05
ZCE67
ZCE13
ZCE66
ZCEH0
ZCE21
ZCE24
ZCE63
ZCE64
ZCE27
ZCE65
ZCE28
ZCE14
Body type
Fixed
design
Compact
Device short name
ZCD
[ui] rated insulation voltage
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
400 V (pollution degree 3) conforming to IEC 60947-1
Series name
Standard compact
Complementary
product compatibility
XCKD
Handle front plate colour
65 mm
Product or component type
Limit switch body
[uimp] rated impulse withstand voltage
4 kV conforming to IEC 60664
4 kV conforming to IEC 60947-1
Associated connection component
ZCDEP16
ZCDEG11
ZCDEN12
ZCDEG13
ZCDEF12
ZCDEP20
Contacts insulation form
Zb
Contacts material
Silver plated contacts
contact operation
Slow-break, break before make
Contacts type and composition
1 NC + 2 NO
body material
Zamak
width (w)
31 mm
contact code designation
R300, DC-13 (Ue = 250 V), Ie = 0.1 A conforming to EN/IEC 60947-5-1 appendix A
C300, AC-15 (Ue = 240 V), Ie = 0.75 A conforming to EN/IEC 60947-5-1 appendix A
depth
30 mm
electrical durability
5000000 cycles, DC-13 120 V, 2 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 3 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Positive opening
With
electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 0.75 mm²
Minimum actuation speed
6 m/s
Poles description
3
Short-circuit protection
6 A cartridge fuse, type gG
Environment
Ambient air temp for storage/transportation
-40…70 °C
Range of product
Telemecanique Limit switches XC Standard
ambient air temperature for operation
-25…70 °C