Limit switch body, Limit switches XC Standard, metal , 2 poles slow break before make M12 - Schneider Electric
47,80 €
SPECIFICATIONS
Main
Associated head ZCE21
ZCE65
ZCE64
ZCE01
ZCE24
ZCE08
ZCE13
ZCE62
ZCEH0
ZCE05
ZCE67
ZCE02
ZCE29
ZCEH2
ZCE63
ZCE28
ZCE27
ZCE11
ZCE14
ZCE10
ZCE66
ZCE06
ZCE07
Body type Fixed
design Compact
Device short name ZCD
[ui] rated insulation voltage 300 V conforming to UL 508
500 V (pollution degree 3) conforming to IEC 60947-1
300 V conforming to CSA C22.2 No 14
Series name Standard compact
Complementary
product compatibility XCKD
Handle front plate colour 65 mm
Product or component type Limit switch body
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
Associated connection component ZCDEG13
ZCDEP16
ZCDEP20
ZCDEG11
ZCDEN12
ZCDEF12
Contacts insulation form Zb
Contacts material Silver plated contacts
contact operation Slow-break, make before break
Contacts type and composition 1 NC + 1 NO
body material Metal
width (w) 31 mm
contact code designation B300, AC-15 (Ue = 240 V), Ie = 1.5 A conforming to EN/IEC 60947-5-1 appendix A
R300, DC-13 (Ue = 250 V), Ie = 0.1 A conforming to EN/IEC 60947-5-1 appendix A
depth 30 mm
electrical durability 5000000 cycles, DC-13 120 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 13 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 9 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Positive opening With
electrical connection Screw-clamp terminals M12, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Minimum actuation speed 6 m/s
Poles description 2
Short-circuit protection 10 A cartridge fuse, type gG
Environment
Ambient air temp for storage/transportation -40…70 °C
Range of product Telemecanique Limit switches XC Standard
ambient air temperature for operation -25…70 °C