Main
Antenna type
Omnidirectional
Device short name
XB5R
Emission class
5M00G7W
number of channels
16
Complementary
Acquisition time
2 ms
electrical composition code
PW1
Antenna gain
0 dBi
Bandwidth
5 MHz
Product certifications
CSA
GOST
CCC
C-Tick
UL
BT 2006/95/EC
response time
< 2 ms
mounting diameter
22 mm
Product or component type
Wireless and batteryless transmitter
bezel material
Plastic
Cad overall depth
43 mm
transmission frequency
2405 MHz
Cad overall height
41.5 mm
Fixing mode
Fixing nut beneath head: 2…2.4 N.m
Operating travel
4.3 mm (total travel)
Cad overall width
30 mm
Max power consumption in w
1 mW
mechanical robustness
Free fall resistance 1000 mm conforming to EN/IEC 60068-2-32
Ik degree of protection
IK03 conforming to IEC 50102
Modulation technique
O-QPSK
Radio agreement
ANATEL
ARIB T66
FCC
ICASA
RSS
Net weight
0.025 kg
communication port protocol
Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4
Embedding depth
42 mm
mechanical durability
1000000 cycles
Maximum sensing distance
100 m in free field
25 m transmitter in a plastic box type XAL D and receiver in a metal enclosure
300 m transmitter in box type XAL D, receiver in metal enclosure and use relay-antenna
Operating force
10 N C/O changing electrical state
Shock resistance
25 gn (duration = 6 ms) for 6000 shocks conforming to IEC 60068-2-27
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Environment
Ambient air temp for storage/transportation
-40…70 °C
Directives
1999/5/EC - R&TTE directive
2004/108/EC - electromagnetic compatibility
ip degree of protection
IP30 (back face) conforming to IEC 60529
Range of product
Harmony XB5
ambient air temperature for operation
-40…70 °C
electromagnetic compatibility
Electrostatic discharge immunity test - test level: 8 kV (in free air (in insulating parts)) conforming to IEC 61000-4-2
Electrostatic discharge immunity test - test level: 4 kV (on contact (on metal parts)) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 20 V/m (80...3000 MHz) conforming to IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 6 V/m (3000...6000 MHz, distance = 20 m) conforming to IEC 61000-4-3
standards
CSA C22.2 No 14
EN/IEC 60947-1
EN/IEC 60947-5-1
UL 508
relative humidity
95 % at -40…70 °C without condensation
vibration resistance
5 gn (f= 11…500 Hz) conforming to IEC 60068-2-6
+/- 10 mm (f= 2…11 Hz) conforming to IEC 60068-2-6