Complementary
Antenna gain
0 dBi
[ics] rated service breaking capacity
4.8 W (per output)
Bandwidth
5 MHz
maximum power consumption in va
20 VA DC
maximum switching current
0.2 mA DC
Product certifications
CCC
CSA
GOST
C-Tick
UL
response time
< 30 ms after transmitter clicks
Handle front plate colour
108 mm
output contacts
4 PNP
Product or component type
Wireless receiver
tightening torque
0.5…1 N.m conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
0.8 kV
[us] rated supply voltage
24 V DC - 15...20 %
maximum voltage drop
<2 V DC at 2 A
minimum switching current
10 mA at 5 V DC
marking
CE
Output type
Transistor PNP
reset time
2 ms time delay
Channels utilisation
1 Harmony Hub per receiver
transmission frequency
2405 MHz
Function of module
Bi-stable
width (w)
36 mm
Max power consumption in w
1 mW
Modulation technique
O-QPSK
Radio agreement
RSS
SRRC
ANATEL
ARIB T66
FCC
ICASA
Net weight
0.13 kg
Operating position
Any position without derating
communication port protocol
Zigbee green power at 2.4 GHz conforming to IEEE 802.15.4
Mounting support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Mounting plate
depth
75 mm
Maximum sensing distance
100 m in free field
25 m transmitter in a plastic box type XAL D and receiver in a metal enclosure
40 m transmitter in box type XAL D, receiver in metal enclosure and use relay-antenna
Housing material
Self-extinguishing plastic
Pollution degree
2 conforming to IEC 60664-1
Time delay range
0.5 s (tolerance: - 15...15 %)
electrical connection
1 conductor cable 0.14…2.5 mm² - AWG 26...AWG 14 - solid - without cable end conforming to IEC 60947-1
2 conductors cable 0.14…1.5 mm² - AWG 26...AWG 16 - solid - without cable end conforming to IEC 60947-1
1 conductor cable 0.14…4 mm² - AWG 26...AWG 12 - flexible - with cable end conforming to IEC 60947-1
2 conductors cable 0.14…1.5 mm² - AWG 26...AWG 16 - flexible - with cable end conforming to IEC 60947-1
maximum power consumption in w
20 W DC
Shock resistance
10 gn (duration = 16 ms) for 6000 shocks conforming to IEC 60068-2-27
Rated short-duration power frequency withstand voltage
1 kV 50 Hz conforming to EN/IEC 60947-5-1
Status led
1 LED green for power ON
1 LED green and yellow for reception signal
4 LEDs green for relay ON
Surge withstand
0.5 kV differential mode conforming to IEC 61000-4-5
1 kV common mode conforming to IEC 61000-4-5
Short-circuit protection
0.4 A fuse type fast blow
Utilisation category
DC-13 conforming to EN/IEC 60947-5-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 (casing) conforming to IEC 60529
IP20 (terminals)
Range of product
Harmony
electromagnetic compatibility
Immunity for industrial environments conforming to EN/IEC 61000-6-2
Conducted and radiated emissions class B conforming to CISPR 22
Electrostatic discharge immunity test - test level: 8 kV (in free air (in insulating parts)) conforming to IEC 61000-4-2
Electrostatic discharge immunity test - test level: 6 kV (on contact (on metal parts)) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80...2000 MHz) conforming to IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 3 V/m (80...2700 MHz, distance = 20 m) conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test - test level: 2 kV (power supply wires) conforming to IEC 61000-4-4
Conducted RF disturbances - test level: 10 V conforming to IEC 61000-4-6
Radiated emission conforming to ETSI EN 300 440-1
Conducted emission conforming to EN 300-489-1
Conducted emission conforming to ETSI EN 300 489-3
Radiated emission conforming to ETSI EN 300 440-2
Electrical fast transient/burst immunity test - test level: 1 kV (PNP output wires) conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test - test level: 0.5 kV (differential mode) conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test - test level: 1 kV (common mode) conforming to IEC 61000-4-5
Immunity to microbreaks and voltage drops - test level: 7 ms conforming to IEC 61000-4-11
overvoltage category
III conforming to IEC 60664-1
standards
EN/IEC 60947-5-1
relative humidity
90 % at -20…55 °C, without condensation conforming to ETSI EN 300 440-1
vibration resistance
+/- 7.5 mm (f= 5…14 Hz) conforming to IEC 60068-2-6
2 gn (f= 8…150 Hz) conforming to IEC 60068-2-6
insulation resistance
> 500 MOhm at 500 V DC conforming to NF C 20-030