Complementary
[ie] rated operational current
1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1
3 A at 120 V, AC-15, B300 conforming to EN/IEC 60947-5-1
0.11 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
6 A conforming to EN/IEC 60947-5-1
Product certifications
CSA
EAC
BV
DNV
CE
LROS (Lloyds register of shipping)
CCC
UL listed
CB Scheme
UKCA
Product or component type
Contact block
tightening torque
0.8…1.2 N.m conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
4 kV conforming to EN 60947-1
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.34 mm² without cable end conforming to EN/IEC 60947-1
Cad overall depth
26 mm
Contacts material
Silver alloy (Ag/Ni)
Cad overall height
41 mm
contact operation
Slow-break
Contacts type and composition
1 NC monitoring contact
Operating travel
1.5 mm (NC changing electrical state)
4.3 mm (total travel)
Cad overall width
10 mm
Sale per indivisible quantity
5
electrical reliability
Λ < 10exp(-7) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 3.4 mA in clean environment conforming to IEC 60947-5-4
Contacts usage
Monitoring contact
Mounting of block
Front mounting
Net weight
0.013 kg
mechanical durability
300000 cycles
electrical durability
300000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, AC-15, 3 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, AC-15, 3 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, DC-13, 0.3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, DC-13, 1 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Device presentation
Basic element
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Operating force
5 N NC changing electrical state
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
25 gn (duration = 6 ms) for 1000 shocks on each axis conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
6 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
Range of product
Harmony XB4
Harmony XB5
ambient air temperature for operation
-40…70 °C
standards
EN/IEC 60947-1
EN/IEC 60947-5-1
IEC 60947-5-4
UL 60947-5-1
CSA C22.2 No 60947-5-1
JIS C8201-1
JIS C8201-5-1
GB/T 14048.5
BS EN 60947-5-1
GOST IEC 60947-5-1
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
25 mm peak to peak (f= 2…10 Hz) conforming to IEC 60068-2-6
protective treatment
TH