Complementary
electrical composition code
C11 (quantity <= 3)
C14 (quantity <= 2)
M10 (quantity <= 2)
[ie] rated operational current
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A300 conforming to EN/IEC 60947-5-1
0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
Product certifications
GL
CSA
BV
LROS (Lloyds register of shipping)
DNV
UL
Product or component type
Contact block
[uimp] rated impulse withstand voltage
4 kV conforming to EN 60947-1
Connections - terminals
Plug-in connector
Contacts material
Silver alloy (Ag/Ni)
contact operation
Slow-break
Contacts type and composition
1 NC
Operating travel
1.5 mm (NC changing electrical state)
4.3 mm (total travel)
Sale per indivisible quantity
5
Contacts usage
Standard contacts
Mounting of block
Front mounting
Net weight
0.011 kg
mechanical durability
10000000 cycles
electrical durability
1000000 cycles, AC-15, 1 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 1.5 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.15 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Device presentation
Basic element
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Operating force
2 N NC changing electrical state
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Short-circuit protection
4 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 conforming to IEC 60529
Range of product
Harmony XB5
Harmony XB4
ambient air temperature for operation
-40…70 °C
standards
CSA C22.2 No 14
UL 508
EN/IEC 60947-1
EN/IEC 60947-5-4
JIS C8201-5-1
EN/IEC 60947-5-1
JIS C8201-1
vibration resistance
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
protective treatment
TH