Complementary
[ie] rated operational current
3 A at 120 V, AC-15, B300
1.5 A at 240 V, AC-15, B300
0.1 A at 250 V, DC-13, R300
0.22 A at 125 V, DC-13, R300
Product certifications
CSA
UL
CCC
GOST
Product or component type
Complete body for illuminated push-button
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1
[us] rated supply voltage
3...24 V
Current consumption
15 mA
Fixing collar material
Plastic
Bulb base
BA 9s
Connections - terminals
Faston connector, connection size: 2.8 x 0.5 mm
Light block supply
Direct
Cad overall depth
40 mm
Contacts material
Silver alloy (Ag/Ni)
Cad overall height
18 mm
contact operation
Slow-break
Contacts type and composition
1 NO + 1 NC
Electrical shock protection class
Class II conforming to IEC 61140
Operating travel
1 mm (NC changing electrical state)
2 mm (NO changing electrical state)
4.3 mm (total travel)
Cad overall width
24 mm
Sale per indivisible quantity
1
electrical reliability
Λ = 10exp(-8) at 5 V and 1 mA with confidence level of 90 % conforming to EN/IEC 60947-5-4
Signalling type
Steady
Contacts usage
Standard
Net weight
0.009 kg
electrical durability
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Operating force
1.6 N NO changing electrical state
2.5 N NC changing electrical state
light source
Incandescent (bulb not included)
Resistance to electrostatic discharge
6 kV on contact (on metal parts) conforming to IEC 61000-2-6
8 kV in free air (in insulating parts) conforming to IEC 61000-2-6
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Resistance to electromagnetic fields
10 V/m conforming to IEC 61000-4-3
Surge withstand
1 kV direct contact conforming to IEC 61000-4-5
2 kV in free air conforming to IEC 61000-4-5
Short-circuit protection
6 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Terminals description iso n°1
(11-12)NC
Environment
Ambient air temp for storage/transportation
-40…70 °C
Range of product
Harmony XB6
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-5-1
JIS C 852
JIS C 4520
EN/IEC 60947-5-5
CSA C22.2 No 14
UL 508
EN/IEC 60947-1
electromagnetic emission
Class B conforming to IEC 55011
vibration resistance
+/- 3 mm (f= 2…500 Hz) conforming to IEC 60068-2-6
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC
resistance to fast transients
2 kV conforming to IEC 61000-4-4