Main
number of channels
2 per receiver
[ui] rated insulation voltage
60 V conforming to IEC 60664-1
Complementary
product compatibility
Radio transmitter XZBWE
[ics] rated service breaking capacity
4.8 W (per output)
maximum switching current
200 mA DC
response time
< 30 ms after sensor change
Handle front plate colour
108 mm
output contacts
4 PNP
Product or component type
Programmable receiver
tightening torque
0.5…1 N.m conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
0.8 kV
[us] rated supply voltage
24 V DC - 15...20 %
maximum voltage drop
<2 V (nominal output current: 200 mA)
minimum switching current
10 mA
marking
CE
Output type
Transistor PNP
Device application
Interface to PLC
Function of module
Receiver unit for remote sensor
width (w)
36 mm
Net weight
0.13 kg
Operating position
Any position without derating
communication port protocol
Zigbee green power at 2.4 GHz
Mounting support
35 mm symmetrical DIN rail conforming to EN/IEC 60715
Mounting plate
depth
75 mm
Maximum number of transceivers
ZigBee: <2
Maximum sensing distance
100 m in free field
25 m in a metal enclosure
Housing material
Self-extinguishing plastic
Pollution degree
2 conforming to IEC 60664-1
Time delay range
0.5 s (tolerance: - 15...15 %)
electrical connection
1 conductor cable 0.14…2.5 mm² AWG 26...AWG 14 solid without cable end conforming to IEC 60947-1
2 conductors cable 0.14…1.5 mm² AWG 26...AWG 16 solid without cable end conforming to IEC 60947-1
1 conductor cable 0.14…4 mm² AWG 26...AWG 12 flexible with cable end conforming to IEC 60947-1
2 conductors cable 0.14…1.5 mm² AWG 26...AWG 16 flexible with cable end conforming to IEC 60947-1
maximum power consumption in w
26 W DC
Shock resistance
10 gn (duration = 16 ms) for 6000 shocks conforming to IEC 60068-2-27
Rated short-duration power frequency withstand voltage
1 kV 50 Hz conforming to EN/IEC 60947-5-1
Starting time
<= 400 ms
Status led
1 LED green for power ON
1 LED green and yellow for reception signal
4 LEDs green for output active
Surge withstand
0.5 kV differential mode conforming to IEC 61000-4-5
1 kV common mode conforming to IEC 61000-4-5
Short-circuit protection
1 A fuse type fast blow
Utilisation category
DC-13 conforming to EN/IEC 60947-5-1
Nominal output current
0.8 A at 24 V DC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20 (casing) conforming to IEC 60529
IP20 (terminals) conforming to IEC 60529
electromagnetic compatibility
Immunity for industrial environments conforming to EN/IEC 61000-6-2
Conducted and radiated emissions class B conforming to CISPR 22
Electrostatic discharge immunity test 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2
Electrostatic discharge immunity test 6 kV on contact (on metal parts) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields 10 V/m, 80 MHz...1 GHz at 3 m conforming to IEC 61000-4-3
Susceptibility to electromagnetic fields 3 V/m, 1.4 MHz…2 GHz at 3 m conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test 2 kV power supply wires conforming to IEC 61000-4-4
Conducted RF disturbances 10 V conforming to IEC 61000-4-6
Radiated emission conforming to ETSI EN 301 489-17
Conducted emission conforming to ETSI EN 301 489-17
Radiated emission conforming to ETSI EN 300 328
Electrical fast transient/burst immunity test 1 kV PNP output wires conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test 0.5 kV differential mode conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test 1 kV common mode conforming to IEC 61000-4-5
Immunity to microbreaks and voltage drops 7 ms conforming to IEC 61000-4-11
overvoltage category
III conforming to IEC 60664-1
standards
EN/IEC 60947-5-1
EN/IEC 60947-1
relative humidity
90 % at -20…55 °C, without condensation conforming to ETSI EN 300 328
vibration resistance
+/- 7.5 mm (f= 5…14 Hz) conforming to IEC 60068-2-6
2 gn (f= 8…150 Hz) conforming to IEC 60068-2-6
insulation resistance
> 500 MOhm at 500 V DC conforming to NF C 20-030