Main
																					
												number of channels
												2 per receiver
											
                            
																					
												[ui] rated insulation voltage
												60 V conforming to IEC 60664-1
											
                            
																			 
																	
										Complementary
																					
												product compatibility
												Radio transmitter XZBWE
											
                            
																					
												[ics] rated service breaking capacity
												4.8 W (per output)
											
                            
																					
												maximum switching current
												200 mA DC
											
                            
																					
												response time
												< 30 ms after sensor change
											
                            
																					
												Handle front plate colour
												108 mm
											
                            
																					
												output contacts
												4 PNP
											
                            
																					
												Product or component type
												Programmable receiver
											
                            
																					
												tightening torque
												0.5…1 N.m conforming to EN/IEC 60947-1
											
                            
																					
												[uimp] rated impulse withstand voltage
												0.8 kV
											
                            
																					
												[us] rated supply voltage
												24 V DC - 15...20 %
											
                            
																					
												maximum voltage drop
												<2 V (nominal output current: 200 mA)
											
                            
																					
												minimum switching current
												10 mA
											
                            
																					
												marking
												CE
											
                            
																					
												Output type
												Transistor PNP
											
                            
																					
												Device application
												Interface to PLC
											
                            
																					
												Function of module
												Receiver unit for remote sensor
											
                            
																					
												width (w)
												36 mm
											
                            
																					
												Net weight
												0.13 kg
											
                            
																					
												Operating position
												Any position without derating
											
                            
																					
												communication port protocol
												Zigbee green power at 2.4 GHz
											
                            
																					
												Mounting support
												35 mm symmetrical DIN rail conforming to EN/IEC 60715
Mounting plate
											
                            
																					
												depth
												75 mm
											
                            
																					
												Maximum number of transceivers
												ZigBee: <2
											
                            
																					
												Maximum sensing distance
												100 m in free field
25 m in a metal enclosure
											
                            
																					
												Housing material
												Self-extinguishing plastic
											
                            
																					
												Pollution degree
												2 conforming to IEC 60664-1
											
                            
																					
												Time delay range
												0.5 s (tolerance: - 15...15 %)
											
                            
																					
												electrical connection
												1 conductor cable 0.14…2.5 mm² AWG 26...AWG 14 solid without cable end conforming to IEC 60947-1
2 conductors cable 0.14…1.5 mm² AWG 26...AWG 16 solid without cable end conforming to IEC 60947-1
1 conductor cable 0.14…4 mm² AWG 26...AWG 12 flexible with cable end conforming to IEC 60947-1
2 conductors cable 0.14…1.5 mm² AWG 26...AWG 16 flexible with cable end conforming to IEC 60947-1
											
                            
																					
												maximum power consumption in w
												26 W DC
											
                            
																					
												Shock resistance
												10 gn (duration = 16 ms) for 6000 shocks conforming to IEC 60068-2-27
											
                            
																					
												Rated short-duration power frequency withstand voltage
												1 kV 50 Hz conforming to EN/IEC 60947-5-1
											
                            
																					
												Starting time
												<= 400 ms
											
                            
																					
												Status led
												1 LED green for power ON
1 LED green and yellow for reception signal
4 LEDs green for output active
											
                            
																					
												Surge withstand
												0.5 kV differential mode conforming to IEC 61000-4-5
1 kV common mode conforming to IEC 61000-4-5
											
                            
																					
												Short-circuit protection
												1 A fuse type fast blow
											
                            
																					
												Utilisation category
												DC-13 conforming to EN/IEC 60947-5-1
											
                            
																					
												Nominal output current
												0.8 A at 24 V DC
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…70 °C
											
                            
																					
												ip degree of protection
												IP20 (casing) conforming to IEC 60529
IP20 (terminals) conforming to IEC 60529
											
                            
																					
												electromagnetic compatibility
												Immunity for industrial environments conforming to EN/IEC 61000-6-2
Conducted and radiated emissions class B conforming to CISPR 22
Electrostatic discharge immunity test 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2
Electrostatic discharge immunity test 6 kV on contact (on metal parts) conforming to IEC 61000-4-2
Susceptibility to electromagnetic fields 10 V/m, 80 MHz...1 GHz at 3 m conforming to IEC 61000-4-3
Susceptibility to electromagnetic fields 3 V/m, 1.4 MHz…2 GHz at 3 m conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test 2 kV power supply wires conforming to IEC 61000-4-4
Conducted RF disturbances 10 V conforming to IEC 61000-4-6
Radiated emission conforming to ETSI EN 301 489-17
Conducted emission conforming to ETSI EN 301 489-17
Radiated emission conforming to ETSI EN 300 328
Electrical fast transient/burst immunity test 1 kV PNP output wires conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test 0.5 kV differential mode conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test 1 kV common mode conforming to IEC 61000-4-5
Immunity to microbreaks and voltage drops 7 ms conforming to IEC 61000-4-11
											
                            
																					
												overvoltage category
												III conforming to IEC 60664-1
											
                            
																					
												standards
												EN/IEC 60947-5-1
EN/IEC 60947-1
											
                            
																					
												relative humidity
												90 % at -20…55 °C, without condensation conforming to ETSI EN 300 328
											
                            
																					
												vibration resistance
												+/- 7.5 mm (f= 5…14 Hz) conforming to IEC 60068-2-6
2 gn (f= 8…150 Hz) conforming to IEC 60068-2-6
											
                            
																					
												insulation resistance
												> 500 MOhm at 500 V DC conforming to NF C 20-030