Main
Device short name
XY2CH
[ithe] thermal current under enclosure
10 A
[ui] rated insulation voltage
400 V (pollution degree 3) conforming to EN/IEC 60947-1
300 V conforming to UL 508
reset
Without
Complementary
[ie] rated operational current
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A
Cable entry number
3 tapped entry for Pg 13.5 cable gland
compatibility code
XY2CH
number of cables
1
Product certifications
UL category NISD emergency stop devices
CCC
Product or component type
Simple stop rope pull switch
tightening torque
0.8…1.2 N.m
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Connections - terminals
Screw clamp terminal, 1 x 0.5...2 x 1.5 mm²
marking
CE
Housing colour
Blue
contact operation
Snap action
Contacts type and composition
1 NC + 1 NO
distance between cable supports
5 m
body material
Zamak
Local signalling
Without pilot light
cover material
Stainless steel
mechanical durability
800000 cycles
Positive opening
With conforming to EN/IEC 60947-5-1
Maximum resistance across terminals
25 MOhm conforming to EN/IEC 60255-7 category 3
25 MOhm conforming to NF C 93-050 method A
trigger cable anchor point
RH or LH side
Shock resistance
50 gn 11 ms conforming to EN/IEC 60068-2-27
Trigger cable maximum length
15 m
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60269
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Telemecanique Emergency stop rope pull switches XY2C
ambient air temperature for operation
-25…70 °C
overvoltage category
Class I conforming to EN/IEC 61140
Class I conforming to NF C 20-030
standards
EN/IEC 60947-5-1
vibration resistance
10 gn (f= 10…150 Hz) conforming to EN/IEC 60068-2-6
protective treatment
TC