Main
Device short name
XY2CE
[ithe] thermal current under enclosure
10 A
[ui] rated insulation voltage
400 V (pollution degree 3) conforming to EN/IEC 60947-1
300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
reset
By booted push-button
Complementary
[ie] rated operational current
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A
Cable entry number
3 plain hole for Pg 13.5 or ISO M20 cable gland
compatibility code
XY2CE
number of cables
1
Product certifications
UL category NISD emergency stop devices
CSA
CCC
Product or component type
Latching emergency stop rope pull switch
tightening torque
0.8…1.2 N.m
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
[us] rated supply voltage
230...240 V AC
Connections - terminals
Screw clamp terminal, 1 x 0.5...2 x 1.5 mm²
Light block supply
Direct
marking
CE
Housing colour
Red RAL 3000
contact operation
Slow-break
Contacts type and composition
2 NC + 2 NO
distance between cable supports
5 m
safety reliability data
B10d = 300000 conforming to IEC 60947-5-5 value given for a life time of 20 years limited by mechanical or contact wear
body material
Zamak
Local signalling
With pilot light, yellow, 230 V
Net weight
1.47 kg
cover material
Stainless steel
mechanical durability
60000 cycles
Positive opening
With conforming to EN/IEC 60947-5-1
Maximum resistance across terminals
25 MOhm conforming to EN/IEC 60255-7 category 3
25 MOhm conforming to NF C 93-050 method A
trigger cable anchor point
RH side
Shock resistance
50 gn 11 ms conforming to EN/IEC 60068-2-27
Safety level
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
Trigger cable maximum length
70 m
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60269
Terminals description iso n°1
(21-22)NC
(13-14)NON
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to IEC 60529
Range of product
Telemecanique Emergency stop rope pull switches XY2C
ambient air temperature for operation
-25…70 °C
overvoltage category
Class I conforming to EN/IEC 61140
Class I conforming to NF C 20-030
standards
EN/ISO 13850
UL 508
EN/IEC 60947-5-5
Work equipment directive 2009/104/EC
EN/IEC 60947-5-1
Machinery directive 2006/42/EC
EN/IEC 60204-1
CSA C22.2 No 14
vibration resistance
10 gn (f= 10…300 Hz) conforming to EN/IEC 60068-2-6
protective treatment
TC