Main
Body type
Fixed
cable length
2 m
Series name
Application
sensor name
XSA
Complementary
[sn] nominal sensing distance
10 mm
cable composition
3 x 0.34 mm²
Adjustable frequency range
6…150 cyc/mn
length [l]
81 mm
Product certifications
UL
CSA
CCC
Product or component type
Sensor
[us] rated supply voltage
12...48 V DC with reverse polarity protection
Current consumption
0...15 mA no-load
maximum voltage drop
<1.8 V (closed)
detection face
Frontal
marking
CE
Device application
Rotation monitoring
Discrete output function
1 NC
Enclosure material
Nickel plated brass
Detector flush mounting acceptance
Flush mountable
Differential travel
3...15% of Fr
Material
Metal
supply voltage limits
10…58 V DC
switching frequency
<= 800 Hz
Net weight
0.3 kg
Discrete output type
PNP
switching capacity in ma
<= 200 mA with overload and short-circuit protection
repeat accuracy
3% of Sr
Front material
PPS
thread type
M30 x 1.5
electrical connection
Cable
output circuit type
DC
Operating zone
0…8 mm
Sensing range
> 8...15 mm
Sensor type
Inductive proximity sensor
Run-up delay at power-up
0 s without
Sensor design
Cylindrical M30
Status led
Output state: 1 LED (red)
Threaded length
67 mm
Wiring technique
3-wire
Size
81 mm
Type of output signal
Discrete
Wire insulation material
PvR
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP67 conforming to IEC 60529
Range of product
Telemecanique Inductive proximity sensors XS
ambient air temperature for operation
-25…70 °C