Main
Safety module application
For dynamic monitoring of double-bodied solenoid valves
Safety module name
XPSPVK
[ui] rated insulation voltage
300 V (pollution degree 2) conforming to IEC 60647-5-1, DIN VDE 0110 part 1
number of additional circuits
4 solid state outputs
Complementary
[ics] rated service breaking capacity
10 mA at 48 V for solid state output circuit
20 mA at 24 V for solid state output circuit
1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
[ith] conventional thermal current
2.5 A
Product certifications
UL
TÜV
CSA
Enclosure type
Removable
Handle front plate colour
73 mm
Product or component type
Preventa safety module
[uimp] rated impulse withstand voltage
4 kV overvoltage category III conforming to IEC 60647-5-1, DIN VDE 0110 part 1
[us] rated supply voltage
24 V DC - 10...10 %
Connections - terminals
Captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² with cable end
Captive screw clamp terminals, 2 x 2.5 mm² without cable end
Associated fuse rating
4 A gG for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
minimum output current
10 mA for relay output
Output type
Relay, 1 NO transfer function + 1 NC feedback loop circuit(s), volt-free
Enclosure material
Polycarbonate
Function of module
Dynamic monitoring of double-bodied solenoid valves
safety reliability data
MTTFd = 90.2 years conforming to EN/ISO 13849-1
DC = 0...99 % conforming to EN/ISO 13849-1
PFHd = 1.25E-8 1/h conforming to EN/IEC 62061
width (w)
152 mm
Local signalling
8 LEDs
Net weight
817.2 g
Maximum response time on input open
40 ms
Mounting support
35 mm symmetrical DIN rail
depth
118 mm
minimum output voltage
17 V for relay output
Power consumption in w
9 W
Number of terminal blocks
32
Safety level
Can reach PL e/category 4 conforming to EN/ISO 13849-1
Can reach SILCL 3 conforming to EN/IEC 62061
Environment
Ambient air temp for storage/transportation
-25…85 °C
ip degree of protection
IP10 (terminals) conforming to EN/IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529
Range of product
Preventa Safety automation
ambient air temperature for operation
-10…55 °C
standards
EN/IEC 60947-5-1
EN 692
EN 60204-1