Complementary
Cable cross section
0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel
0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end
0.5…1 mm² - AWG 20...AWG 18 flexible cablewith cable end, with double bezel
maximum switching current
6 A
Product certifications
cULus
TÜV
RCM
Handle front plate colour
99 mm
Product or component type
Safe relay output module
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 61800-5-1
[us] rated supply voltage
24 V - 20...20 % DC
Connections - terminals
1 spring clamp terminals, removable terminal block
2 spring clamp terminals, removable terminal block
minimum switching current
20 mA
Associated fuse rating
3.5 A, slow-blow
Output type
Relay, 4 NO circuit(s), volt-free
Quantity per set
1
maximum power dissipation in w
3 W
Function of module
Monitoring safety actuators for relay output
safety reliability data
B10d = 300000 utilisation category AC-15 230 V, , <3 A conforming to EN/ISO 13849-1
B10d = 750000 utilisation category AC-15 230 V, , <1 A conforming to EN/ISO 13849-1
B10d = 10000000 utilisation category DC-13 24 V, , <2 A conforming to EN/ISO 13849-1
width (w)
22.5 mm
number of outputs
4 relay
Local signalling
1 LED green with PWR marking for power ON
1 LED green with RUN marking for RUN (status)
1 LED red with E IN marking for internal error
1 LED red with E EX marking for external error
2 LEDs orange with ADDR marking for node address
4 LEDs green/red with RELAY K1...K4 marking for relay contact
4 LEDs yellow with RST marking for reset
Net weight
0.3 kg
Discrete output number
8 solid state at 125 mA (diagnostics)
Integrated connection type
Backplane expansion bus
Mounting support
Omega 35 mm DIN rail conforming to EN 50022
depth
114.5 mm
mechanical durability
20000000 cycles
electrical durability
20000000 cycles
Pollution degree
2
electrical connection
Spring terminal
Number of terminal blocks
4
Maximum switching voltage
400 V AC
250 V DC
Insulation
250 V AC between power supply and housing conforming to EN/IEC 61800-5-1
Shock resistance
10 gn for 16 ms (1000 shocks on each axis) conforming to EN/IEC 61496-1
Safety level
Can reach category 4 conforming to EN/ISO 13849-1
Can reach PL = e conforming to EN/ISO 13849-1
Can reach SIL 3 conforming to EN/IEC 61508
SILCL 3 conforming to IEC 62061
Switching time
12 ms
Environment
Ambient air temp for storage/transportation
-20…85 °C
ip degree of protection
IP20
Range of product
Preventa Safety automation
ambient air temperature for operation
-10…55 °C
electromagnetic compatibility
Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
overvoltage category
II
standards
IEC 62061
EN/IEC 61508
EN/ISO 13849-1
EN/IEC 61800-5-1
quality labels
CE
relative humidity
10…95 %
vibration resistance
+/-0.35 mm (f= 10…55 Hz) conforming to EN/IEC 61496-1