Main
Device short name
XPSMCM
service life
20 year(s)
Complementary
range compatibility
Preventa XPSMCM
Cable cross section
0.2…1.5 mm² - AWG 24...AWG 16 flexible cablewithout cable end
0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end
0.25…1 mm² - AWG 23...AWG 18 flexible cablewith cable end, without bezel
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel
0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel
0.5…1.5 mm² - AWG 20...AWG 16 flexible cablewith cable end, with double bezel
0.2…1 mm² - AWG 24...AWG 18 solid cablewithout cable end
0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end
Product certifications
cULus
RCM
TÜV
Handle front plate colour
99 mm
Product or component type
Non-safe communication module
[us] rated supply voltage
24 V - 20...20 % DC
Current consumption
0.125 mA
Connections - terminals
2 captive screw clamp terminals, removable terminal block
width (w)
22.5 mm
Local signalling
LED green with PWR marking for power ON
LED green with RUN marking for operating
LED red with E IN marking for internal error
LED red with E EX marking for external error
LED green/red with STS marking for communication status
LED green/red with Mode marking for connection state
Net weight
0.3 kg
Maximum cable distance between devices
1000 m
100 m
1200 m
400 m
200 m
communication port protocol
Profibus DP
Mounting support
Omega 35 mm DIN rail conforming to EN 50022
connector type
female SUB-D 9
depth
114.5 mm
power dissipation in w
3 W
Number of port
1
Pollution degree
2
Insulation
250 V AC between power supply and housing conforming to EN/IEC 61800-5-1
Shock resistance
10 gn (duration = 16 ms) for 1000 shocks on each axis conforming to EN/IEC 61496-1
Method of access
Server
Transmission rate
500 kbit/s
9.6 kbit/s
19.2 kbit/s
45.45 kbit/s
93.75 kbit/s
187.5 kbit/s
1.5 kbit/s
3 Mbit/s
6 Mbit/s
12 Mbit/s
Environment
Ambient air temp for storage/transportation
-20…85 °C
ip degree of protection
IP20
operating altitude
2000 m
Range of product
Modicon MCM
ambient air temperature for operation
-10…55 °C
electromagnetic compatibility
Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to EN/IEC 61000-4-2
Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to EN/IEC 61000-4-2
Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to EN/IEC 61000-4-3
Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
overvoltage category
II
quality labels
CE
relative humidity
10…95 %
vibration resistance
+/-0.35 mm (f= 10…55 Hz) conforming to EN/IEC 61496-1