Complementary
maximum switching current
250 mA
Product certifications
EAC
cULus
Adjustable range of switching point on falling pressure
0.2…3.88 MPa
2…38.8 bar
199.95…3881.75 kPa
Handle front plate colour
93 mm
Product or component type
Electronic pressure sensors
[uimp] rated impulse withstand voltage
0.5 kV DC
[us] rated supply voltage
24 V DC SELV (voltage limits: 17…33 V)
Adjustable range of switching point on rising pressure
319.92…3998.96 kPa
0.32…4 MPa
3.2…40 bar
Current consumption
<= 50 mA
maximum voltage drop
2 V
marking
CE
Contacts type and composition
2 NO/NC programmable
Drift of the sensitivity
+/- 0.03 % of measuring range/°C
Drift of the zero point
+/- 0.1 % of measuring range/°C
width (w)
41 mm
Destruction pressure
150 bar
14996.10 kPa
15 MPa
Local signalling
2 LEDs (yellow) for light ON when switch is actuated
Display accuracy
<= 1 % of the measuring range
Net weight
0.19 kg
Discrete output type
Solid state PNP, 2 NO/NC programmable
Display response time type
Fast 50 ms
Normal 200 ms
Slow 600 ms
Maximum delay first up
300 ms
Operating position
Any position, but disposals can falsified the measurement in case of upside down mounting
Display type
4 digits 7 segments
depth
42 mm
mechanical durability
10000000 cycles
repeat accuracy
<= 0.2 % of the measuring range
Front material
Polyester
Housing material
Polyacrylamide
316L stainless steel
Materials in contact with fluid
Fluorocarbon FKM (Viton)
Ceramic
316L stainless steel
electrical connection
Male connector M12, 4 pins
Maximum permissible accidental pressure
14996.10 kPa
150 bar
15 MPa
Measurement accuracy on switching output
<= 0.6 % of the measuring range
Shock resistance
50 gn conforming to EN/IEC 60068-2-27
Response time on output
<= 5 ms for discrete output
Minimum differential travel
1.2 bar
119.97 kPa
120 kPa
Overall accuracy
<= 1 % of the measuring range
Scale type
Fixed differential
Type of output signal
Discrete
Protection type
Reverse polarity
Overvoltage protection
Short-circuit protection
Overload protection
Switching output time delay
0...50 s in steps of 1 second
Environment
Ambient air temp for storage/transportation
-40…80 °C
ip degree of protection
IP65 conforming to EN/IEC 60529
IP67 conforming to EN/IEC 60529
Range of product
Telemecanique Pressure sensors XM
ambient air temperature for operation
-20…80 °C
electromagnetic compatibility
Susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
Surge immunity test: 1 kV conforming to EN/IEC 61000-4-5
Electrical fast transient/burst immunity test: 2 kV conforming to EN/IEC 61000-4-4
Electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2
standards
UL 61010-1
EN/IEC 61326-2-3
vibration resistance
20 gn (f= 10…2000 Hz) conforming to EN/IEC 60068-2-6