Main
Fluid connection type
SAE 7/16-20UNF-2B (female) with schrader
controlled fluid
Fresh water (0-135 °C), air (-40-135 °C), hydraulic oil (-40-135 °C), gas (-40-135 °C), refrigeration fluid (-40-135 °C)
Type of packing
Individual
pressure sensor name
XMLP
pressure sensor type
Pressure transmitter
Complementary
Accuracy
0.1 % of the measuring range
local display
Without
Product certifications
CERCMcULus
Product or component type
Electronic pressure sensors
[us] rated supply voltage
12...24 V DC SELV (voltage limits: 7-33 V)
Analogue output function
4...20 mA, 2-wire
Current consumption
< 23 mA
Quantity per set
Set of 1
Drift of the sensitivity
+/- 0,02 % of measuring range/°K
Drift of the zero point
+/- 0,02 % of measuring range/°K
Electrical circuit type
Control circuit
measurement accuracy
+/- 0,5 % de la plage de mesure
Operating position
Any position
Materials in contact with fluid
Stainless steel type AISI 303
electrical connection
1 male connector EN 175301-803-A (ex DIN43650) 3 pins
Shock resistance
100 gn for 11 ms conforming to IEC 60068-2-27
Response time on output
<= 2 ms 10...90 % of full scale
Type of output signal
Analogue
Protection type
Load short-circuitreverse polarity
Environment
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Telemecanique Pressure sensors XM
electromagnetic compatibility
Electrostatic discharge immunity test conforming to IEC 61000-4-2 8 kV air, 4 kV contact, 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 1 kV 42 Ohm, immunity to magnetic fields conforming to IEC 61000-4-8 100 A/m 50 Hz, electrical fast transient/burst immunity test conforming to IEC 61000-4-4 4 kV, susceptibility to electromagnetic fields conforming to IEC 61000-4-3 10 V/m 80...3000 MHz, radiated RF fields conforming to IEC 61000-4-6 10 V 0.01...80 MHz
standards
IEC 61326-2-3NSF ANSI 61
vibration resistance
20 gn (f = 15-2000 Hz) conforming to IEC 60068-2-6
protective treatment
TC