Main
Fluid connection type
G 1/4A (male) conforming to DIN 3852-E
controlled fluid
Air (0…80 °C)
Fresh water (0…80 °C)
Type of packing
Individual
pressure sensor name
XMLK
pressure rating
16 bar
pressure sensor type
Pressure transmitter
Complementary
length [l]
67.5 mm
local display
Without
Product certifications
EAC
UL 508
RCM
CSA C22.2 No 14
Product or component type
Electronic pressure sensors
[uimp] rated impulse withstand voltage
0.5 kV
[us] rated supply voltage
24 V DC SELV (voltage limits: 8…33 V)
Analogue output function
4...20 mA, 2-wire
Current consumption
< 20 mA
nema degree of protection
NEMA 4
diameter
36 mm
Quantity per set
Set of 1
Drift of the sensitivity
+/- 0.04 % of measuring range/°K
Drift of the zero point
+/- 0.03 % of measuring range/°K
pressure setting range
0…16 bar
Destruction pressure
48 bar
Electrical circuit type
Control circuit
Net weight
0.11 kg
measurement accuracy
+/- 1 % of the measuring range
Operating position
Any position
Long term stability
+/- 1 % of the measuring range
mechanical durability
10000000 cycles
Materials in contact with fluid
Stainless steel type AISI 303
Ceramic
Nitrile (NBR)
electrical connection
1 male connector EN 175301-803-A (ex DIN43650) 4 pins
Maximum permissible accidental pressure
32 bar
Resolution
0.1 % of the measuring range
Shock resistance
25 gn for 11 ms conforming to EN/IEC 60068-2-27
Response time on output
< 5 ms
Scale type
Fixed differential
Type of output signal
Analogue
Protection type
Load short-circuit
Reverse polarity
Environment
Ambient air temp for storage/transportation
-25…80 °C
ip degree of protection
IP65 conforming to EN/IEC 60529
Range of product
Telemecanique Pressure sensors XM
ambient air temperature for operation
0…80 °C
electromagnetic compatibility
Electrostatic discharge immunity test conforming to EN/IEC 61000-4-2 8 kV air, 6 kV contact
Susceptibility to electromagnetic fields conforming to EN/IEC 61000-4-3 10 V/m 80...1000 MHz
Electrical fast transient/burst immunity test conforming to EN/IEC 61000-4-4 2 kV
1.2/50 µs shock waves immunity test conforming to EN/IEC 61000-4-5 500 V 12 Ohm, 1 kV 42 Ohm
Radiated RF fields conforming to EN/IEC 61000-4-6 10 V 0.15...80 MHz
Immunity to magnetic fields conforming to EN/IEC 61000-4-8 30 A/m 50 Hz
standards
CE
EN/IEC 61326-2-3
vibration resistance
20 gn (f = 9…2000 Hz) conforming to EN/IEC 60068-2-6
protective treatment
TC