Main
Fluid connection type
G 1/4A (male) conforming to DIN 3852-E
controlled fluid
Air (-15…125 °C)
Corrosive fluid (-15…125 °C)
Hydraulic oil (-15…125 °C)
Fresh water (0…125 °C)
Type of packing
Individual
pressure sensor name
XMLG
pressure rating
-1 bar
pressure sensor type
Pressure transmitter
Complementary
length [l]
48.5 mm
local display
Without
Product certifications
EAC
UL 508
CSA C22.2 No 14
Handle front plate colour
58.1 mm
Product or component type
Electronic pressure sensors
[uimp] rated impulse withstand voltage
0.5 kV
[us] rated supply voltage
12 V DC (voltage limits: 8…33 V)
24 V DC (voltage limits: 8…33 V)
Analogue output function
4...20 mA, 2 wires
Current consumption
< 20 mA
nema degree of protection
NEMA 4
diameter
22.8 mm
Quantity per set
Set of 1
Drift of the sensitivity
+/- 0.015 % of measuring range/°C
Drift of the zero point
+/- 0.015 % of measuring range/°C
pressure setting range
-1…0 bar
Destruction pressure
3 bar
Electrical circuit type
Control circuit
Net weight
0.095 kg
measurement accuracy
+/- 0.3 % of the measuring range
Operating position
Any position
mechanical durability
10000000 cycles
repeat accuracy
+/- 0.1 % of the measuring range
Materials in contact with fluid
Stainless steel type AISI 303
FPM (Viton)
Ceramic
electrical connection
1 male connector M12, 3 pins
Maximum permissible accidental pressure
2.7 bar
Resistance to electrostatic discharge
15 kV in air conforming to EN/IEC 61000-4-2
8 kV on contact conforming to EN/IEC 61000-4-2
Shock resistance
25 gn for 11 ms conforming to EN/IEC 60068-2-27
Response time on output
< 2 ms
Resistance to electromagnetic fields
200 V/m 80…1000 Hz conforming to EN/IEC 61000-4-3
Surge withstand
1 kV 42 Ohm conforming to EN/IEC 61000-4-5
500 kV 12 Ohm conforming to EN/IEC 61000-4-5
Scale type
Fixed differential
Type of output signal
Analogue
Protection type
Load short-circuit
Reverse polarity
Environment
Ambient air temp for storage/transportation
-40…85 °C
ip degree of protection
IP66 conforming to EN/IEC 60529
IP67 conforming to EN/IEC 60529
Range of product
Telemecanique Pressure sensors XM
ambient air temperature for operation
-15…85 °C
Resistance to conducted disturbances
30 V (0.15…80 Hz) conforming to EN/IEC 61000-4-6
standards
CE
EN/IEC 61326-2-3
vibration resistance
20 gn (f= 9…2000 Hz) conforming to EN/IEC 60028-2-6
protective treatment
TC
resistance to fast transients
4 kV conforming to EN/IEC 61000-4-4
resistance to magnetic fields
30 A/m 50 Hz conforming to EN/IEC 61000-4-8