All categories
Compare Cart

XMLD020B1S12 - Pressure switch XMLD 20 bar 2 stages fixed scale 2 C/O - Schneider Electric

Expected in 2-4 weeks
XMLD020B1S12 - Pressure switch XMLD 20 bar 2 stages fixed scale 2 C/O - Schneider Electric - Pressure switch XMLD 20 bar 2 stages fixed scale 2 C/O - Schneider Electric - 0
XMLD020B1S12 - Pressure switch XMLD 20 bar 2 stages fixed scale 2 C/O - Schneider Electric
388,29 € excl. VAT
473,71 € incl. VAT
Text About:
Pressure switch XMLD 20 bar 2 stages fixed scale 2 C/O - Schneider Electric
473,71 €
SPECIFICATIONS
Main
Device short name XMLD
pressure actuator Diaphragm
Fluid connection type G 1/4 (female) conforming to ISO 228
product specific application Dual stage
[ui] rated insulation voltage 300 V conforming to UL 508
500 V conforming to EN/IEC 60947-1
300 V conforming to CSA C22.2 No 14
controlled fluid Air (0…160 °C)
Fresh water (0…160 °C)
Hydraulic oil (0…160 °C)
Pressure switch type of operation Detection of 2 single thresholds
pressure rating 20 bar
pressure sensor type Electromechanical pressure sensor
Complementary
[in] rated current 3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1
1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1
0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1
local display Without
Product certifications CSA
UL
EAC
Handle front plate colour 113 mm
Product or component type Electromechanical pressure sensor
[uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-1
awg gauge AWG 20...AWG 14
cable entry Cable gland 7…13 mm
Enclosure material Zinc alloy
Contacts type and composition 2 C/O snap action, silver contacts
2 C/O staggered, silver contacts
Electrical shock protection class Class I conforming to IEC 1140
Class I conforming to IEC 536
Class I conforming to NF C 20-030
width (w) 46 mm
Destruction pressure 90 bar
Electrical circuit type Control circuit
Net weight 0.705 kg
setting External
Operating position Any position
terminal block type 8 terminals
depth 85 mm
mechanical durability 5000000 cycles
repeat accuracy 2 %
Materials in contact with fluid Brass
FPM, FKM
electrical connection Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²
Maximum operating rate 120 cyc/mn
Maximum resistance across terminals 25 mOhm conforming to IEC 255-7 category 3
25 mOhm conforming to NF C 93-050 method A
Maximum permissible accidental pressure 45 bar
Maximum permissible pressure - per cycle 25 bar
Natural differential at high setting 1.3 bar
Natural differential at low setting 0.7 bar
Shock resistance 50 gn conforming to IEC 60068-2-27
Scale type Fixed differential
Spread between 2 stages 1.24…9.55 bar
Short-circuit protection 10 A cartridge fuse, type gG (gl)
Environment
Ambient air temp for storage/transportation -40…70 °C
ip degree of protection IP66 conforming to EN/IEC 60529
Range of product Telemecanique Pressure sensors XM
ambient air temperature for operation -25…70 °C
standards UL 508
EN/IEC 60947-5-1
CSA C22.2 No 14
CE
vibration resistance 4 gn conforming to IEC 60068-2-6 (f = 30…500 Hz)
protective treatment TC standard version
Recently viewed
388,29 € excl. VAT
473,71 € incl. VAT
Expected in 2-4 weeks