Main
Device short name
XMLC
pressure actuator
Diaphragm
Fluid connection type
G 1/4 (female) conforming to ISO 228
product specific application
-
[ui] rated insulation voltage
300 V conforming to UL 508
500 V conforming to EN/IEC 60947-1
300 V conforming to CSA C22.2 No 14
controlled fluid
Corrosive fluid (0…160 °C)
Pressure switch type of operation
Regulation between 2 thresholds
pressure rating
10 bar
pressure sensor type
Electromechanical pressure sensor
Complementary
[in] rated current
3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1
1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1
0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1
local display
With
Product certifications
UL
CSA
EAC
Adjustable range of switching point on falling pressure
0.25…9.3 bar
Auxiliary contacts operation
Simultaneous, snap action
Handle front plate colour
113 mm
Product or component type
Electromechanical pressure sensor
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Adjustable range of switching point on rising pressure
0.7…10 bar
awg gauge
AWG 20...AWG 14
cable entry
Cable gland 7…13 mm
Contacts material
Silver contacts
Enclosure material
Zinc alloy
Contacts type and composition
2 C/O
Electrical shock protection class
Class I conforming to IEC 1140
Class I conforming to IEC 536
Class I conforming to NF C 20-030
width (w)
46 mm
Destruction pressure
45 bar
Electrical circuit type
Control circuit
Net weight
0.685 kg
setting
External
Operating position
Any position
terminal block type
8 terminals
depth
85 mm
mechanical durability
5000000 cycles
repeat accuracy
2 %
Materials in contact with fluid
316L stainless steel
PTFE
electrical connection
Screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²
Maximum operating rate
120 cyc/mn
Maximum resistance across terminals
25 mOhm conforming to IEC 255-7 category 3
25 mOhm conforming to NF C 93-050 method A
Maximum permissible accidental pressure
22.5 bar
Maximum permissible pressure - per cycle
12.5 bar
Possible differential maximum at high setting
8 bar
Possible differential minimum at high setting
0.7 bar (+/- 0.01 bar)
Possible differential minimum at low setting
0.45 bar (+/- 0.05 bar)
Shock resistance
50 gn conforming to IEC 60068-2-27
Scale type
Adjustable differential
Short-circuit protection
10 A cartridge fuse, type gG (gl)
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to EN/IEC 60529
Range of product
Telemecanique Pressure sensors XM
ambient air temperature for operation
-25…70 °C
standards
UL 508
CSA C22.2 No 14
EN/IEC 60947-5-1
CE
vibration resistance
4 gn conforming to IEC 60068-2-6 (f = 30…500 Hz)
protective treatment
TC standard version