Main
																					
												Device short name
												XMLB
											
                            
																					
												pressure actuator
												Diaphragm
											
                            
																					
												Fluid connection type
												G 1/4 (female) conforming to ISO 228
											
                            
																					
												product specific application
												-
											
                            
																					
												[ui] rated insulation voltage
												300 V conforming to UL 508
500 V conforming to EN/IEC 60947-1
300 V conforming to CSA C22.2 No 14
											
                            
																					
												controlled fluid
												Air (0…70 °C)
Fresh water (0…70 °C)
Hydraulic oil (0…70 °C)
											
                            
																					
												Pressure switch type of operation
												Regulation between 2 thresholds
											
                            
																					
												pressure rating
												5 bar
											
                            
																					
												pressure sensor type
												Electromechanical vacuum-pressure sensor
											
                            
																			 
																	
										Complementary
																					
												[in] rated current
												3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1
1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1
0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1
											
                            
																					
												local display
												With
											
                            
																					
												Product certifications
												BV
EAC
CSA
LROS (Lloyds register of shipping)
CCC
UL
											
                            
																					
												Adjustable range of switching point on falling pressure
												-1…4.5 bar
											
                            
																					
												Auxiliary contacts operation
												Snap action
											
                            
																					
												Handle front plate colour
												113 mm
											
                            
																					
												Product or component type
												Electromechanical pressure sensor
											
                            
																					
												[uimp] rated impulse withstand voltage
												6 kV conforming to EN/IEC 60947-1
											
                            
																					
												Adjustable range of switching point on rising pressure
												-0.5…5 bar
											
                            
																					
												Contacts material
												Silver contacts
											
                            
																					
												Enclosure material
												Zinc alloy
											
                            
																					
												Contacts type and composition
												1 C/O
											
                            
																					
												Electrical shock protection class
												Class I conforming to IEC 1140
Class I conforming to IEC 536
Class I conforming to NF C 20-030
											
                            
																					
												width (w)
												35 mm
											
                            
																					
												Destruction pressure
												23 bar
											
                            
																					
												Electrical circuit type
												Control circuit
											
                            
																					
												Net weight
												0.715 kg
											
                            
																					
												setting
												External
											
                            
																					
												Operating position
												Any position
											
                            
																					
												terminal block type
												4 terminals
											
                            
																					
												depth
												75 mm
											
                            
																					
												mechanical durability
												3000000 cycles
											
                            
																					
												repeat accuracy
												2 %
											
                            
																					
												Materials in contact with fluid
												Zinc alloy
Nitrile
304L stainless steel
											
                            
																					
												electrical connection
												1 male connector EN 175301-803-A (ex DIN43650), 4 pins
											
                            
																					
												Maximum operating rate
												120 cyc/mn
											
                            
																					
												Maximum resistance across terminals
												25 mOhm conforming to IEC 255-7 category 3
25 mOhm conforming to NF C 93-050 method A
											
                            
																					
												Maximum permissible accidental pressure
												11.25 bar
											
                            
																					
												Maximum permissible pressure - per cycle
												6.25 bar
											
                            
																					
												Possible differential maximum at high setting
												6 bar
											
                            
																					
												Possible differential minimum at high setting
												0.5 bar (+/- 0.05 bar)
											
                            
																					
												Possible differential minimum at low setting
												0.5 bar (+/- 0.05 bar)
											
                            
																					
												Shock resistance
												50 gn conforming to IEC 60068-2-27
											
                            
																					
												Scale type
												Adjustable differential
											
                            
																					
												Short-circuit protection
												10 A cartridge fuse, type gG (gl)
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-40…70 °C
											
                            
																					
												ip degree of protection
												IP65 conforming to EN/IEC 60529
											
                            
																					
												Range of product
												Telemecanique Pressure sensors XM
											
                            
																					
												ambient air temperature for operation
												-25…70 °C
											
                            
																					
												standards
												CSA C22.2 No 14
UL 508
CE
EN/IEC 60947-5-1
											
                            
																					
												vibration resistance
												4 gn conforming to IEC 60068-2-6 (f = 30…500 Hz)
											
                            
																					
												protective treatment
												TC standard version