Main
Device short name
XMLA
pressure actuator
Diaphragm
Fluid connection type
G 1/4 (female) conforming to ISO 228
product specific application
-
[ui] rated insulation voltage
300 V conforming to UL 508
500 V conforming to EN/IEC 60947-1
300 V conforming to CSA C22.2 No 14
controlled fluid
Corrosive fluid (0…160 °C)
Pressure switch type of operation
Detection of 1 single threshold
pressure rating
2.5 bar
pressure sensor type
Electromechanical pressure sensor
Complementary
[in] rated current
3 A, B300, AC-15 (Ue = 120 V) conforming to EN/IEC 60947-5-1
1.5 A, B300, AC-15 (Ue = 240 V) conforming to EN/IEC 60947-5-1
0.1 A, R300, DC-13 (Ue = 250 V) conforming to EN/IEC 60947-5-1
local display
With
Product certifications
EAC
CCC
CSA
LROS (Lloyds register of shipping)
UL
BV
Adjustable range of switching point on falling pressure
0.02…2.37 bar
Auxiliary contacts operation
Snap action
Handle front plate colour
158 mm
Product or component type
Electromechanical pressure sensor
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Adjustable range of switching point on rising pressure
0.15…2.5 bar
Contacts material
Silver contacts
Enclosure material
Zinc alloy
Contacts type and composition
1 C/O
Electrical shock protection class
Class I conforming to IEC 1140
Class I conforming to IEC 536
Class I conforming to NF C 20-030
width (w)
35 mm
Destruction pressure
18 bar
Electrical circuit type
Control circuit
Net weight
1.01 kg
setting
External
Operating position
Any position
depth
77.5 mm
mechanical durability
8000000 cycles
repeat accuracy
2 %
Materials in contact with fluid
316L stainless steel
PTFE
electrical connection
1 male connector EN 175301-803-A (ex DIN43650), 4 pins
Maximum operating rate
120 cyc/mn
Maximum resistance across terminals
25 mOhm conforming to IEC 255-7 category 3
25 mOhm conforming to NF C 93-050 method A
Maximum permissible accidental pressure
9 bar
Maximum permissible pressure - per cycle
5 bar
Natural differential at high setting
0.13 bar (+/- 0.03 bar)
Natural differential at low setting
0.13 bar (+/- 0.03 bar)
Shock resistance
50 gn conforming to IEC 60068-2-27
Scale type
Fixed differential
Short-circuit protection
10 A cartridge fuse, type gG (gl)
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP65 conforming to EN/IEC 60529
Range of product
Telemecanique Pressure sensors XM
ambient air temperature for operation
-25…70 °C
standards
CE
EN/IEC 60947-5-1
CSA C22.2 No 14
UL 508
vibration resistance
4 gn conforming to IEC 60068-2-6 (f = 30…500 Hz)
protective treatment
TC standard version