Main
[ithe] thermal current under enclosure
10 A
contact block application
Single speed
[ui] rated insulation voltage
600 V (pollution degree 3) conforming to IEC 60947-1
component name
XENG
contact block type
Single
Complementary
product compatibility
XACA9...head
XACA
Product or component type
Contact block
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
Connections - terminals
Screw clamp terminals, 1 x 0.5...1 x 2.5 mm² without cable end
Screw clamp terminals, 1 x 0.5...2 x 1.5 mm² with cable end
contact operation
Slow-break
Simultaneous
Contacts type and composition
1 NC + 2 NO
rated operational power in w
40 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
48 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
65 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Type of operator
Spring return
Electrical circuit type
Control circuit
contact code designation
A600 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A
A600 AC-15, Ue = 600 V, Ie = 1.2 A conforming to IEC 60947-5-1 appendix A
Q600 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
Q600 DC-13, Ue = 600 V, Ie = 0.1 A conforming to IEC 60947-5-1 appendix A
Mounting of block
Front mounting
Net weight
0.04 kg
mechanical durability
1000000 cycles
Maximum resistance across terminals
25 MOhm
Operating force
18 N
Shock resistance
100 gn conforming to IEC 60068-2-27
Short-circuit protection
10 A fuse protection by cartridge fuse type gG
Terminals description iso n°1
(21-22)NC
(13-14)NON
(33-34)NON
Environment
Ambient air temp for storage/transportation
-40…70 °C
Range of product
Harmony XAC
ambient air temperature for operation
-25…70 °C
overvoltage category
Class II conforming to IEC 61140
standards
EN/IEC 60947-5-1
CSA C22.2 No 14
UL 508
vibration resistance
15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6