All categories
Compare Cart

XEND4801 - Latching contact block 1 NC + 1 NO front mounting, 40 mm centres - Schneider Electric

Expected in 2-4 weeks
XEND4801 - Latching contact block 1 NC + 1 NO front mounting, 40 mm centres - Schneider Electric - Latching contact block 1 NC + 1 NO front mounting, 40 mm centres - Schneider Electric - 0
XEND4801 - Latching contact block 1 NC + 1 NO front mounting, 40 mm centres - Schneider Electric
77,28 €
77,28 € incl. VAT
Text About:
Latching contact block 1 NC + 1 NO front mounting, 40 mm centres - Schneider Electric
77,28 €
SPECIFICATIONS
Main
[ithe] thermal current under enclosure 10 A
contact block application Single speed
[ui] rated insulation voltage 500 V (pollution degree 3) conforming to IEC 60947-1
component name XEND
contact block type Double
Complementary
product compatibility XACB
XACM
Product or component type Contact block
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-1
Connections - terminals Screw clamp terminals, 1 x 2.5 mm² with or without cable end
Screw clamp terminals, 2 x 1.5 mm² with or without cable end
contact operation Slow-break
Contacts type and composition 1 NC + 1 NO
rated operational power in w 42 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
45 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
60 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Type of operator 1 latching
1 spring return
Electrical circuit type Control circuit
rated operational power in va 140 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 24 V 50/60 Hz, load factor = 0.5 (inductive load)
385 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 48 V 50/60 Hz, load factor = 0.5 (inductive load)
455 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 230 V 50/60 Hz, load factor = 0.5 (inductive load)
525 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 127 V 50/60 Hz, load factor = 0.5 (inductive load)
contact code designation A300 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A
Q300 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
Mounting of block Front mounting
Net weight 0.17 kg
mechanical durability 1000000 cycles
Maximum resistance across terminals 25 MOhm
Mechanical interlocking Without mechanical interlock
Shock resistance 100 gn conforming to IEC 60068-2-27
Terminal identifier (11-12)NC
(13-14)NON
Terminals description iso n°2 (11-12)NC
B
(23-24)NON
Short-circuit protection 10 A fuse protection by cartridge fuse type gG
Terminals description iso n°1 (11-12)NC
B
(23-24)NON
Environment
Ambient air temp for storage/transportation -40…70 °C
Range of product Harmony XAC
ambient air temperature for operation -25…70 °C
standards EN 60947-5-1
CSA C22.2 No 14
IEC 60947-5-1
vibration resistance 15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
Recently viewed
77,28 €
77,28 € incl. VAT
Expected in 2-4 weeks