Main
Device short name
XE2S
[ui] rated insulation voltage
300 V conforming to UL 508
500 V (pollution degree 3) conforming to IEC 60947-1
300 V conforming to CSA C22.2 No 14
Series name
Standard format
Complementary
product compatibility
XCKS
XCKP
XCKJ
XCKD
XCKM
Associated body
ZCKS
ZCP61
ZCKJ
ZCD61
ZCKM
Product or component type
Limit switch contact block
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
Contacts insulation form
Zb
Contacts material
Silver with gold flashed contacts
contact operation
Snap action
Contacts type and composition
1 NO + 1 NC
contact code designation
A300 (Ue = <= 48 V), Ie = 10 mA, Ithe = 10 A
Q300 (Ue = >= 5 V), Ie = 1 mA
electrical durability
5000000 cycles, DC-13 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Positive opening
With
electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm²
Maximum resistance across terminals
25 mOhm conforming to IEC 60255-7 category 3
Minimum actuation speed
0.01 mm/s
Poles description
2
Short-circuit protection
10 A cartridge fuse, type gG
Environment
Range of product
Telemecanique Limit switches XC Standard