Main
Device short name
XE2N
[ui] rated insulation voltage
300 V conforming to UL 508
500 V (pollution degree 3) conforming to IEC 60947-1
300 V conforming to CSA C22.2 No 14
Series name
Standard format
Complementary
Product or component type
Limit switch contact block
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
Contacts insulation form
Zb
Contacts material
Silver plated contacts
contact operation
Slow-break, break before make
Contacts type and composition
1 NO + 1 NC
contact code designation
A300, AC-15 (Ue = 240 V), Ie = 3 A, Ithe = 10 A conforming to EN/IEC 60947-5-1 appendix A
Q300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to EN/IEC 60947-5-1 appendix A
electrical durability
5000000 cycles, DC-13 120 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 24 V, 13 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13 48 V, 9 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Positive opening
With
electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Maximum resistance across terminals
25 mOhm conforming to IEC 60255-7 category 3
Minimum actuation speed
6 m/min
Poles description
2
Short-circuit protection
10 A cartridge fuse, type gG
Environment
Range of product
Telemecanique Limit switches XC Standard