Complementary
[ie] rated operational current
6 A at 120 V, AC-15, A300 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
Product certifications
CSA
UL
Handle front plate colour
115 mm
Product or component type
Safety switch
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
Actuator forcible withdrawal rtc
10 N
cable entry
2 entries tapped for 1/2" NPT
Locking options description
Without locking of actuator
contact operation
Slow-break, simultaneous
Contacts type and composition
3 NC
Electrical shock protection class
Class II conforming to EN/IEC 61140
safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
body material
PA (polyamide)
Material
Plastic
width (w)
52 mm
Net weight
0.16 kg
head material
PA (polyamide)
depth
30 mm
mechanical durability
1000000 cycles
Maximum actuation speed
0.5 m/s
Positive opening
With NC contact
electrical connection
Terminal, clamping capacity: 1 x 0.5...2 x 1.5 mm² with or without cable end
Maximum operating rate
10 cyc/mn for maximum durability
Minimum actuation speed
0.01 m/s
Insulation
Double insulated
Positive opening minimum force
15 N
Shock resistance
10 gn for 11 ms conforming to IEC 60068-2-27
Poles description
3
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
Short-circuit protection
10 A cartridge fuse type gG (gl)
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Range of product
Telemecanique Safety switches XCS
ambient air temperature for operation
-25…70 °C
standards
EN/ISO 12100
EN 1088/ISO 14119
CSA C22.2 No 14
EN/IEC 60204-1
EN/IEC 60947-5-1
UL 508
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC