All categories
Compare Cart

XCSPL583 - Guard switch, Telemecanique Safety switches XCS, XCSPL, elbowed flush lever, centred, 1NC+1 NO 1/2"N - Schneider Electric

Expected in 2-4 weeks
XCSPL583 - Guard switch, Telemecanique Safety switches XCS, XCSPL, elbowed flush lever, centred, 1NC+1 NO 1/2"N - Schneider Electric - Guard switch, Telemecanique Safety switches XCS, XCSPL, elbowed flush lever, centred, 1NC+1 NO 1/2"N - Schneider Electric - 0
XCSPL583 - Guard switch, Telemecanique Safety switches XCS, XCSPL, elbowed flush lever, centred, 1NC+1 NO 1/2"N - Schneider Electric
71,27 €
71,27 € incl. VAT
Text About:
Guard switch, Telemecanique Safety switches XCS, XCSPL, elbowed flush lever, centred, 1NC+1 NO 1/2"N - Schneider Electric
71,27 €
SPECIFICATIONS
Main
[ithe] thermal current under enclosure 10 A
Operator direction information Centred
[ui] rated insulation voltage 300 V conforming to UL 508
300 V conforming to CSA C22.2 No 14
500 V (pollution degree 3) conforming to EN/IEC 60947-1
component name XCSPL
head type Turret head rotary lever
Complementary
Product certifications UL
BG
CSA
Handle front plate colour 161 mm
Product or component type Guard switch
[uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-5-1
cable entry 1 entry tapped for 1/2" NPT
cable outer diameter 7…10 mm
Enclosure material Polyamide PA66 fibre glass impregnated
Clamping connection capacity 1 x 0.5...2 x 1.5 mm² with or without cable end
contact operation Slow-break, break before make
Contacts type and composition 1 NC + 1 NO
Electrical shock protection class Class II conforming to EN/IEC 61140
safety reliability data B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
Material Plastic
width (w) 30 mm
Type of operator Elbowed flush lever
contact code designation A300, AC-15 (Ue = 120 V, Ie = 6 A) conforming to EN/IEC 60947-5-1
A300, AC-15 (Ue = 240 V, Ie = 3 A) conforming to EN/IEC 60947-5-1
Q300, DC-13 (Ue = 125 V, Ie = 0.55 A) conforming to EN/IEC 60947-5-1
Q300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1
Net weight 0.095 kg
Lever material Stainless steel
depth 30 mm
mechanical durability 1000000 cycles
Positive opening With NC contact
electrical connection Terminal
Maximum resistance across terminals 30 mOhm conforming to EN/IEC 60947-5-4
Minimum torque for tripping 0.1 N.m
Insulation Double insulated
Positive opening minimum torque 0.25 N.m
Shock resistance 50 gn for 11 ms conforming to IEC 60068-2-27
Poles description 2
Safety level Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to IEC 61508
Short-circuit protection 10 A cartridge fuse type gG (gl)
Tripping angle 5 °
Environment
Ambient air temp for storage/transportation -40…70 °C
ip degree of protection IP67 conforming to IEC 60529
Range of product Telemecanique Safety switches XCS
ambient air temperature for operation -25…70 °C
standards EN 1088/ISO 14119
EN/IEC 60204-1
UL 508
EN/ISO 12100
EN/IEC 60947-5-1
EN/IEC 60947-5-4
CSA C22.2 No 14
vibration resistance 50 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment TC
TH
Recently viewed
71,27 €
71,27 € incl. VAT
Expected in 2-4 weeks