Complementary
[ie] rated operational current
3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
Product certifications
UL
CSA
Handle front plate colour
94 mm
Product or component type
Safety switch
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
Actuator forcible withdrawal rtc
10 N
cable entry
1 entry tapped for Pg 11
Locking options description
Without locking of actuator
cable outer diameter
7…10 mm
contact operation
Snap action
Contacts type and composition
1 NC + 1 NO
Electrical shock protection class
Class II conforming to EN/IEC 61140
safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
body material
PA (polyamide)
Material
Plastic
width (w)
30 mm
Net weight
0.11 kg
head material
PA (polyamide)
depth
30 mm
mechanical durability
1000000 cycles
Maximum actuation speed
0.5 m/s
Positive opening
With NC contact
electrical connection
Terminal, clamping capacity: 1 x 0.34...2 x 1.5 mm²
Maximum operating rate
10 cyc/mn for maximum durability
Minimum actuation speed
0.01 m/s
Insulation
Double insulated
Positive opening minimum force
15 N
Shock resistance
10 gn for 11 ms conforming to IEC 60068-2-27
Poles description
2
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
Short-circuit protection
10 A cartridge fuse type gG (gl)
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP67 conforming to EN/IEC 60529
IP67 conforming to EN/IEC 60947-5-1
Range of product
Telemecanique Safety switches XCS
ambient air temperature for operation
-25…70 °C
standards
UL 508
EN/IEC 60204-1
EN 1088/ISO 14119
EN/ISO 12100
EN/IEC 60947-5-1
CSA C22.2 No 14
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC