Complementary
[ie] rated operational current
0.55 A at 125 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
0.75 A at 240 V, AC-15, C300 conforming to EN/IEC 60947-5-1
1.5 A at 120 V, AC-15, C300 conforming to EN/IEC 60947-5-1
cable composition
4 x 0.5 mm²
Product certifications
UL
cUL
CSA
Handle front plate colour
87 mm
Product or component type
Safety switch
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
Actuator forcible withdrawal rtc
8 N
Locking options description
Without locking of actuator
contact operation
Slow-break, simultaneous
Contacts type and composition
2 NC
Electrical shock protection class
Class II conforming to EN/IEC 61140
safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
body material
PA (polyamide)
Material
Plastic
width (w)
15 mm
Net weight
0.11 kg
head material
PA (polyamide)
depth
30 mm
mechanical durability
1000000 cycles
Maximum actuation speed
1.5 m/s
Positive opening
With NC contact
electrical connection
Pre-cabled
Maximum operating rate
20 cyc/mn for maximum durability
Minimum actuation speed
0.05 m/s
Insulation
Double insulated
Minimum actuator force for extraction
8 N
Shock resistance
50 gn for 11 ms conforming to IEC 60068-2-27
Poles description
2
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
Short-circuit protection
10 A cartridge fuse type gG (gl)
Environment
Ambient air temp for storage/transportation
-25…80 °C
ip degree of protection
IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Range of product
Telemecanique Safety switches XCS
ambient air temperature for operation
-25…70 °C
standards
EN/ISO 12100
EN/IEC 60204-1
CSA C22.2 No 14
EN/IEC 60947-5-1
EN 1088/ISO 14119
UL 508
vibration resistance
6 gn (f= 10…55 Hz) conforming to IEC 60068-2-6
protective treatment
TC