Complementary
[ie] rated operational current
0.55 A at 24 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.75 A at 240 V, AC-15, C300 conforming to EN/IEC 60947-5-1
[un] rated nominal voltage
24 V - 15...10 %
Product certifications
UL
CSA
TÜV
Handle front plate colour
205 mm
Product or component type
Safety switch
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-5-1
Load factor
1
cable entry
3 entries tapped for 1/2" NPT
Locking options description
With interlocking, locking by solenoid
minimum switching current
10 mA at 20 °C
contact operation
Slow-break, break before make
Contacts type and composition
1 NC + 2 NO
Electrical shock protection class
Class I conforming to EN/IEC 61140
safety reliability data
B10d = 5500000 value given for a life time of 20 years limited by mechanical or contact wear
body material
Zamak
Material
Metal
width (w)
44 mm
Local signalling
1 LED (orange) for actuator withdrawn
1 LED (green) for actuator inserted and locked
Net weight
1.1 kg
head material
Zamak
depth
51 mm
Electromagnet interlocking
Locking on energisation and unlocking on de-energisation of solenoid
mechanical durability
1000000 cycles
Maximum actuation speed
0.5 m/s
Positive opening
With NC contact
electrical connection
Spring terminal, clamping capacity: 1 x 1.5 mm² flexible or solid cable
Spring terminal, clamping capacity: 2 x 0.5 mm² flexible cables with 13 mm bared ends
Maximum operating rate
10 cyc/mn for maximum durability
Minimum actuation speed
0.01 m/s
minimum switching voltage
17 V
Maximum actuator forcible withdrawal rtc
3000 N
Maximum load current
<= 15 A
Minimum actuator force for extraction
20 N
Shock resistance
10 gn for 11 ms conforming to IEC 60068-2-27
Poles description
3
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 conforming to EN/IEC 61508
Supply frequency
50/60 Hz
Signalling circuit type
AC/DC
Resistance to mechanical impact
9.6 J against the partition
6.4 J without partition
Short-circuit protection
4 A cartridge fuse type gG (gl)
6 A type fast blow
Supply voltage type
AC/DC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
IP67
Range of product
Telemecanique Safety switches XCS
ambient air temperature for operation
-25…60 °C
standards
UL 508
EN/ISO 13849-1
EN/IEC 60947-5-1
EN/IEC 60204-1
EN 1088/ISO 14119
CSA C22.2 No 14
EN/IEC 62061
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC