Complementary
[ie] rated operational current
0.55 A at 125 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1
3 A at 120 V, AC-15, B300 conforming to EN/IEC 60947-5-1
1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1
[un] rated nominal voltage
24 V - 20...10 %
Product certifications
UL
CSA
Handle front plate colour
146 mm
Product or component type
Safety switch
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
Actuator forcible withdrawal rtc
2000 N
Load factor
1
cable entry
2 entries tapped for 1/2" NPT
Locking options description
With interlocking, locking by solenoid
contact operation
Slow-break, break before make
Contacts type and composition
2 NC + 1 NO
Electrical shock protection class
Class I conforming to EN/IEC 61140
safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
body material
Zamak
Material
Metal
width (w)
98 mm
Local signalling
2 LEDs (green or orange) for guard open/guard closed and locked
Net weight
1.14 kg
head material
Zamak
depth
44 mm
Electromagnet interlocking
Locking on energisation and unlocking on de-energisation of solenoid
mechanical durability
1000000 cycles
Maximum actuation speed
0.5 m/s
Positive opening
With NC contact
Power consumption in va
10 VA inrush
10 VA sealed
electrical connection
Terminal, clamping capacity: 1 x 0.5...2 x 1.5 mm² with or without cable end
Maximum operating rate
10 cyc/mn for maximum durability
Minimum actuation speed
0.01 m/s
Minimum actuator force for extraction
20 N
Shock resistance
10 gn for 11 ms conforming to IEC 60068-2-27
Poles description
3
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508
Supply frequency
50/60 Hz
Signalling circuit type
AC/DC
Short-circuit protection
10 A cartridge fuse type gG (gl)
Protection type
Overvoltage protection for signalling circuit
Signalling circuit consumption
7 mA
Supply voltage type
AC/DC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Range of product
Telemecanique Safety switches XCS
ambient air temperature for operation
-25…40 °C
standards
CSA C22.2 No 14
EN/IEC 60947-5-1
EN/IEC 60204-1
EN/ISO 12100
EN 1088/ISO 14119
UL 508
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC