Main
Device short name
XCSA
[ithe] thermal current under enclosure
10 A
[ui] rated insulation voltage
300 V conforming to UL 508
500 V conforming to EN/IEC 60947-1
300 V conforming to CSA C22.2 No 14
head type
Key operated turret head
Complementary
Cable entry number
1 tapped entry for M20 x 1.5 cable gland (included) 7…13 mm
Product certifications
IEC-Ex INE 17.0020X
INERIS 04ATEX0014X
Product or component type
Safety switch
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-5-1
Locking options description
Without locking of actuator
marking
II2 D-Ex tb IIIC T85°C Db IP67
Cad overall depth
44 mm
Cad overall height
114 mm
Clamping connection capacity
1 x 0.5...2 x 1.5 mm² with or without cable end
contact operation
Slow-break, break before make
Contacts type and composition
1 NC + 2 NO
Electrical shock protection class
Class I conforming to EN/IEC 60536
safety reliability data
B10d = 5000000 value given for a life time of 20 years limited by mechanical or contact wear
body material
Zamak
Cad overall width
40 mm
Material
Metal
Local signalling
Without
contact code designation
A300, AC-15 (Ue = 120 V, Ie = 6 A) conforming to EN/IEC 60947-5-1
A300, AC-15 (Ue = 240 V, Ie = 3 A) conforming to EN/IEC 60947-5-1
Q300, DC-13 (Ue = 125 V, Ie = 0.55 A) conforming to EN/IEC 60947-5-1
Q300, DC-13 (Ue = 250 V, Ie = 0.27 A) conforming to EN/IEC 60947-5-1
Net weight
0.44 kg
head material
Zamak
mechanical durability
1000000 cycles
Maximum actuation speed
0.5 m/s
Positive opening
With NC contact
electrical connection
Terminal
Maximum operating rate
10 cyc/mn for maximum durability
Minimum actuation speed
0.01 m/s
Minimum actuator force for extraction
20 N
Shock resistance
10 gn for 11 ms conforming to IEC 60068-2-27
Poles description
3
Safety level
Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1
Can reach SIL 3 with the appropriate monitoring system and correctly wired conforming to IEC 61508
Short-circuit protection
10 A cartridge fuse type gG (gl)
Environment
Ambient air temp for storage/transportation
-40…70 °C
Directives
2014/34/EU - ATEX directive
ip degree of protection
IP67 conforming to EN/IEC 60529 and EN/IEC 60947-5-1
Range of product
Telemecanique Safety switches XCS
ambient air temperature for operation
-25…70 °C
Dust zone
Zone 21 - 22
standards
EN/IEC 60079-31
EN/IEC 60079-0
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC