Complementary
[ie] rated operational current
1.5 A at 240 V, AC-15 conforming to EN/IEC 60947-5-1 appendix A
0.1 A at 250 V, DC-13 conforming to EN/IEC 60947-5-1 appendix A
Product certifications
UL
CSA
CCC
Handle front plate colour
50 mm
Product or component type
Limit switch
[uimp] rated impulse withstand voltage
2.5 kV conforming to IEC 60664
2.5 kV conforming to IEC 60947-1
Contacts insulation form
Za
contact operation
Snap action
Contacts type and composition
1 C/O
Electrical shock protection class
Class I conforming to IEC 61140
Class I conforming to NF C 20-030
Fixing mode
By the body
body material
Zamak
Material
Metal
width (w)
30 mm
Type of operator
Spring return plunger metal
Ik degree of protection
IK06 conforming to EN 62262
Net weight
0.085 kg
head material
Zamak
depth
16 mm
mechanical durability
10000000 cycles
electrical durability
5000000 cycles, DC-13, 24 V, 3 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, 48 V, 2 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, 120 V, 1 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Maximum actuation speed
0.5 m/s
Positive opening
Without
electrical connection
Male connector M12, 4 pins
Maximum resistance across terminals
25 mOhm conforming to IEC 60255-7 category 3
Minimum actuation speed
0.01 m/min
Minimum force for tripping
8.5 N
Movement of operating head
Linear
Switch actuation
On end
Type of approach
Vertical approach, 1 direction
Shock resistance
25 gn for 18 ms conforming to IEC 60068-2-27
Poles description
1
Sensor design
Miniature
Short-circuit protection
4 A cartridge fuse, type gG
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to IEC 60529
IP67 conforming to IEC 60529
IP68 conforming to IEC 60529
Range of product
Telemecanique Limit switches XC Standard
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-5-1
EN/IEC 60204-1
CSA C22.2 No 14
UL 508
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC