Product certifications
CSA
UL
Handle front plate colour
81 mm
Product or component type
Limit switch
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
cable entry
3 entries tapped for M20 x 1.5 cable gland, cable outer diameter: 7…13 mm
Contacts insulation form
Zb
contact operation
Slow-break, break before make
Contacts type and composition
2 x (1 NC + 1 NO)
Electrical shock protection class
Class I conforming to IEC 61140
Class I conforming to NF C 20-030
Fixing mode
By the body
body material
Zamak
Material
Metal
width (w)
77 mm
Type of operator
Spring return roller lever thermoplastic
Ik degree of protection
IK05 conforming to EN 50102
Net weight
0.43 kg
depth
36 mm
mechanical durability
3000000 cycles
electrical durability
5000000 cycles, DC-13, inductive load type, 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, inductive load type, 24 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, inductive load type, 48 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Maximum actuation speed
1.5 m/s
Number of steps
1
Positive opening
With
electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.34...2 x 1.5 mm²
Maximum resistance across terminals
25 MOhm conforming to IEC 60255-7 category 3
Minimum actuation speed
6 m/min
Minimum torque for tripping
0.2 N.m
Movement of operating head
Rotary
Switch actuation
By 30° cam
Positive opening minimum torque
0.5 N.m
Type of approach
Lateral approach, 2 directions
Shock resistance
50 gn for 11 ms conforming to EN/IEC 60068-2-27
Poles description
4
Terminals description iso n°1
(21-22)NC
(13-14)NON
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to EN/IEC 60529
Range of product
Telemecanique Limit switches XC Standard
ambient air temperature for operation
-25…70 °C
standards
EN 60947-5-1
IEC 60204-1
IEC 60947-5-1
EN 60204-1
CSA C22.2 No 14
UL 508
vibration resistance
25 gn (f= 10…500 Hz) conforming to EN/IEC 60068-2-6
protective treatment