Complementary
Product certifications
UL
CSA
CCC
Handle front plate colour
64 mm
Product or component type
Limit switch
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60664
6 kV conforming to IEC 60947-1
cable entry
3 entries tapped for Pg 11 cable gland
Contacts insulation form
Zb
Contacts type and composition
1 NC + 1 NO
Electrical shock protection class
Class I conforming to IEC 61140
Class I conforming to NF C 20-030
Fixing mode
By the body
body material
Zamak
Material
Metal
width (w)
64 mm
Ik degree of protection
IK05 conforming to EN 50102
contact code designation
A300, AC-15 (Ue = 240 V), Ie = 3 A conforming to EN/IEC 60947-5-1 appendix A
Q300, DC-13 (Ue = 250 V), Ie = 0.27 A conforming to EN/IEC 60947-5-1 appendix A
depth
30 mm
mechanical durability
20000000 cycles
electrical durability
5000000 cycles, DC-13, inductive load type, 120 V, 4 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, inductive load type, 24 V, 7 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
5000000 cycles, DC-13, inductive load type, 48 V, 10 W, operating rate <60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C
Maximum actuation speed
0.5 m/s
Number of steps
1
Positive opening
With
electrical connection
Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm²
Maximum resistance across terminals
25 MOhm conforming to IEC 60255-7 category 3
Minimum actuation speed
6 m/min
Switch actuation
By 30° cam
Type of approach
Lateral approach
Shock resistance
50 gn for 11 ms conforming to EN/IEC 60068-2-27
Poles description
2
Short-circuit protection
10 A cartridge fuse, type gG
Terminals description iso n°1
(13-14)NON !@ !(21-22)NC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to EN/IEC 60529
Range of product
Telemecanique Limit switches XC Standard
ambient air temperature for operation
-25…70 °C
standards
EN 60204-1
IEC 60204-1
EN 60947-5-1
CSA C22.2 No 14
IEC 60947-5-1
UL 508
vibration resistance
25 gn (f= 10…500 Hz) conforming to EN/IEC 60068-2-6
protective treatment
TC