Complementary
[ie] rated operational current
3 A at 120 V, AC-15, B300 conforming to EN/IEC 60947-5-1
1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1
0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1
Product certifications
UL
CCC
CSA
GOST
Handle front plate colour
18 mm
mounting diameter
16 mm
Product or component type
Complete illuminated push-button
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1
[us] rated supply voltage
12...24 V AC/DC
Current consumption
15 mA
nema degree of protection
NEMA 13 conforming to UL 50
NEMA 4 conforming to UL 50
NEMA 4X conforming to UL 50
NEMA 13 conforming to CSA C22.2 No 94
NEMA 4 conforming to CSA C22.2 No 94
NEMA 4X conforming to CSA C22.2 No 94
Bulb base
Integral LED
Connections - terminals
Faston connectors, connection size: 2.8 x 0.5 mm
bezel material
Plastic
Contacts material
Silver alloy (Ag/Ni)
contact operation
Slow-break
Contacts type and composition
1 NC
Electrical shock protection class
Class II conforming to IEC 61140
Operating travel
2 mm (NC changing electrical state)
3.5 mm (total travel)
Sale per indivisible quantity
1
width (w)
24 mm
electrical reliability
Λ = 10exp(-8) at 5 V and 1 mA with confidence level of 90 % conforming to IEC 60947-5-4
Signalling type
Steady
supply voltage limits
6…30 V AC/DC
Type of operator
latching
Net weight
0.022 kg
Operating position
Any position
depth
57 mm
electrical durability
1000000 cycles, AC-15 at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13 at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Shape of signaling unit head
Rectangular
Operating force
4.5 N NC changing electrical state
Operator profile
Red flush, unmarked
light source
LED
Resistance to electrostatic discharge
6 kV on contact (on metal parts) conforming to IEC 61000-4-2
8 kV in free air (in insulating parts) conforming to IEC 61000-4-2
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Resistance to electromagnetic fields
10 V/m conforming to IEC 61000-4-3
Surge withstand
1 kV direct contact conforming to IEC 61000-4-5
2 kV in free air conforming to IEC 61000-4-5
Short-circuit protection
6 A cartridge fuse type gG
Terminals description iso n°1
(21-22)NC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Harmony XB6
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-1
UL 508
JIS C 852
CSA C22.2 No 14
EN/IEC 60947-5-5
EN/IEC 60947-5-1
JIS C 4520
electromagnetic emission
Class B conforming to IEC 55011
vibration resistance
+/- 3 mm (f= 2…500 Hz) conforming to IEC 60068-2-6
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC
resistance to fast transients
2 kV conforming to IEC 61000-4-4