Main
Device short name
XB6
[ui] rated insulation voltage
250 V (pollution degree 2) conforming to EN/IEC 60947-1
Complementary
Cap/operator or lens colour
Red
Product certifications
GOST
CSA
CCC
UL
Handle front plate colour
18 mm
mounting diameter
16 mm
Product or component type
Complete pilot light
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1
[us] rated supply voltage
12...24 V AC/DC
Current consumption
15 mA
nema degree of protection
NEMA 13 conforming to UL 50
NEMA 4 conforming to UL 50
NEMA 4X conforming to UL 50
NEMA 13 conforming to CSA C22.2 No 94
NEMA 4 conforming to CSA C22.2 No 94
NEMA 4X conforming to CSA C22.2 No 94
Bulb base
Integral LED
Connections - terminals
Faston connectors, connection size: 2.8 x 0.5 mm
Light block supply
Direct
bezel material
Plastic
Electrical shock protection class
Class II conforming to IEC 61140
Sale per indivisible quantity
1
width (w)
18 mm
Signalling type
Steady
supply voltage limits
6…30 V AC/DC
Net weight
0.015 kg
Operating position
Any position
depth
57 mm
Shape of signaling unit head
Round
light source
LED
Resistance to electrostatic discharge
6 kV on contact (on metal parts) conforming to IEC 61000-4-2
8 kV in free air (in insulating parts) conforming to IEC 61000-4-2
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Resistance to electromagnetic fields
10 V/m conforming to IEC 61000-4-3
Surge withstand
1 kV direct contact conforming to IEC 61000-4-5
2 kV in free air conforming to IEC 61000-4-5
Terminals description iso n°1
(+ -)PL
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Harmony XB6
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-5-1
CSA C22.2 No 14
JIS C 852
UL 508
EN/IEC 60947-1
JIS C8201-5-1
EN/IEC 60947-5-5
JIS C8201-1
electromagnetic emission
Class B conforming to EN 55011
vibration resistance
+/- 3 mm (f= 2…500 Hz) conforming to IEC 60068-2-6
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
protective treatment
TC
resistance to fast transients
2 kV conforming to IEC 61000-4-4