Complementary
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
Cap/operator or lens colour
Red
Product certifications
UL listed
CSA
BV
DNV
LROS (Lloyds register of shipping)
GL
Handle front plate colour
42 mm
mounting diameter
22 mm
Product or component type
Illuminated push-button
tightening torque
0.8…1.2 N.m conforming to EN 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
[us] rated supply voltage
<= 250 V
Fixing collar material
Plastic
nema degree of protection
NEMA 13
NEMA 4X
Bulb base
BA 9s
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1
Light block supply
Direct <2.4 W
bezel material
Dark grey plastic
Contacts material
Silver alloy (Ag/Ni)
Operator additional information
With plain lens
contact operation
Slow-break
Contacts type and composition
1 NO + 1 NC
Operating travel
1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state)
4.3 mm (total travel)
Sale per indivisible quantity
1
width (w)
30 mm
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4
Signalling type
Steady
Type of operator
spring return
Ik degree of protection
IK05 conforming to IEC 50102
Contacts usage
Standard contacts
Net weight
0.057 kg
depth
54 mm
mechanical durability
10000000 cycles
electrical durability
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Device presentation
Complete product
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Shape of signaling unit head
Round
Resistance to high pressure washer
7000000 Pa at 55 °C, distance : 0.1 m
Operating force
3.5 N NC changing electrical state
3.8 N
Operator profile
Red flush, unmarked
light source
Bulb not included
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Terminals description iso n°1
(13-14)NON !@ !(21-22)NC