Complementary
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
Product certifications
INERIS 04ATEX9004U
mounting diameter
22 mm
Product or component type
Complete emergency stop push-button
tightening torque
0.8…1.2 N.m conforming to EN 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-1
Fixing collar material
Zamak
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN 60947-1
marking
Ex tb IIIC
bezel material
Chromium plated metal
Contacts material
Silver alloy (Ag/Ni)
contact operation
Slow-break
Contacts type and composition
1 NO + 1 NC
Fixing mode
Screw-fixed: 0.8…1.2 N.m
Operating travel
1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state)
4.3 mm (total travel)
Sale per indivisible quantity
1
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4
Type of operator
trigger action and mechanical latching
Ik degree of protection
IK05
Contacts usage
Standard
Embedding depth
43 mm
Fixing center
>= 30 x 40 mm (support panel) - thickness: 1…6 mm
mechanical durability
300000 cycles
electrical durability
1000000 cycles AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Shape of signaling unit head
Round
Operating force
50 N
Operator profile
Red mushroom Ø 40 mm
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
Directives
94/9/EC - ATEX directive
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Harmony XB4
ambient air temperature for operation
-20…60 °C
Dust zone
Zone 21 - 22
overvoltage category
I conforming to IEC 60536
standards
EN/IEC 60947-5-5
EN 60079-0:2009
EN 60079-31:2009
EN 61000-6-2
EN/ISO 13850
IEC 60079-0:2007
IEC 60079-31:2008
vibration resistance
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
protective treatment
TH