Complementary
[ie] rated operational current
1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1
3 A at 120 V, AC-15, B300 conforming to EN/IEC 60947-5-1
0.11 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
6 A conforming to EN/IEC 60947-5-1
Product certifications
CSA
BV
UL listed
LROS (Lloyds register of shipping)
DNV
CE
CCC
CB Scheme
UKCA
EAC
Handle front plate colour
47 mm
mounting diameter
22 mm
Product or component type
Emergency switching off push-button
Emergency stop push-button
tightening torque
0.8…1.2 N.m conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1
4 kV conforming to 86/188/EEC
Fixing collar material
Zamak
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.34 mm² without cable end conforming to EN/IEC 60947-1
bezel material
Chromium plated metal
Contacts material
Silver alloy (AgNi)
Silver alloy (AgSnO2)
contact operation
Slow-break
Electrical shock protection class
Class I conforming to IEC 60536
Fixing mode
By fixing collar recommended torque: 1 N.m (+/- 0.2 N.m)
Operating travel
1.5 mm (NC changing electrical state)
4.3 mm (total travel)
Sale per indivisible quantity
1
width (w)
40 mm
electrical reliability
Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 3.4 mA in clean environment conforming to EN/IEC 60947-5-4
Type of operator
trigger action and mechanical latching
Ik degree of protection
IK06 conforming to IEC 60068-2-75
Contacts usage
Monitoring contact
Standard contacts
Net weight
0.126 kg
depth
85 mm
mechanical durability
300000 cycles
electrical durability
300000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, AC-15, 3 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, AC-15, 3 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, DC-13, 0.3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
300000 cycles, DC-13, 1 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Device presentation
Complete product
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Shape of signaling unit head
Round
Operating force
47 N
Operator profile
Red mushroom Ø 40 mm, unmarked
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
25 gn (duration = 6 ms) for 1000 shocks on each axis conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
6 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP66 conforming to IEC 60529
IP67 conforming to IEC 60529
IP69 conforming to IEC 60529
IP69K conforming to ISO 20653
Type 13 conforming to UL 50E
Type 12 conforming to UL 50E
Type 4 conforming to UL 50E
Type 4X conforming to UL 50E
Range of product
Harmony XB4
ambient air temperature for operation
-40…70 °C
standards
EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-5
EN/IEC 60204-1
IEC 60947-5-4
IEC 60364-5-53
EN/ISO 13850
UL 60947-5-1
CSA C22.2 No 60947-5-1
JIS C8201-1
JIS C8201-5-1
GB/T 14048.5
BS EN 60947-5-1
GOST IEC 60947-5-1
vibration resistance
5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
25 mm peak to peak (f= 2…10 Hz) conforming to IEC 60068-2-6
protective treatment
TH