Complementary
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
Product certifications
GL
DNV
INERIS 04ATEX9004U
mounting diameter
22 mm
Product or component type
Complete push-button
tightening torque
0.8…1.2 N.m conforming to EN 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Fixing collar material
Zamak
nema degree of protection
NEMA 13
NEMA 4X
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1
marking
Ex tb IIIC
bezel material
Chromium plated metal
Contacts material
Silver alloy (Ag/Ni)
Operator additional information
Booted (coloured silicon)
contact operation
Slow-break
Contacts type and composition
1 NO
Operating travel
2.6 mm (NO changing electrical state)
4.3 mm (total travel)
Sale per indivisible quantity
1
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4
Type of operator
spring return
Ik degree of protection
IK03 conforming to IEC 50102
Embedding depth
43 mm
Fixing center
>= 30 x 40 mm (support panel)
mechanical durability
5000000 cycles
electrical durability
1000000 cycles AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1: appendix C
Positive opening
Without
Shape of signaling unit head
Round
Resistance to high pressure washer
7000000 Pa at 55 °C, distance : 0.1 m
Operating force
3.8 N NO changing electrical state
Operator profile
Black projecting
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
Directives
94/9/EC - ATEX directive
ip degree of protection
IP66 conforming to IEC 60529
IP67
IP69
IP69K
Range of product
Harmony XB4
ambient air temperature for operation
-40…70 °C
Dust zone
Zone 21 - 22
overvoltage category
I conforming to IEC 60536
standards
EN 50014
EN 50281-1-1
IEC 61241-0
IEC 61241-1
vibration resistance
5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6
protective treatment
TH