Complementary
electrical insulation class
Class II conforming to IEC 61140
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
Product certifications
UL listed
CSA
Product or component type
Complete control station
tightening torque
0.8…1.2 N.m conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
[us] rated supply voltage
24 V AC/DC
Colour of base of enclosure
Light grey (RAL 7035)
cable entry
1 knock-out for cable entry 0…14 mm
2 knock-outs for Pg 13 cable gland and ISO M20 0…12 mm
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
Contacts material
Silver alloy (Ag/Ni)
contact operation
Slow-break
Operating travel
1.5 mm (NC changing electrical state)
4.3 mm (total travel)
Material
Polycarbonate
Colour of cover
Yellow (RAL 1021)
Control station application
Emergency switching off function
Emergency stop function
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA conforming to EN/IEC 60947-5-4
Ik degree of protection
IK05 conforming to EN 50102
Control station composition
1 mushroom head Ø 40 mm push-button, red 1 NO + 2 NC
Net weight
0.180 kg
mechanical durability
300000 cycles
electrical durability
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Resistance to high pressure washer
7000000 Pa at 55 °C, distance : 0.1 m
Operating force
44 N
Operator profile
1 mushroom head push-button
Operators description
Red unmarked 1 NO + 2 NC
Product destination
For XB5 Ø 22 mm control and signalling units
Resistance to electrostatic discharge
4 kV on contact (on metal parts) conforming to IEC 61000-4-2
8 kV in free air (in insulating parts)
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
25 gn (duration = 6 ms) for 1000 shocks on each axis conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1