Main
Device short name
XALE
[ui] rated insulation voltage
250 V (pollution degree 3) conforming to EN/IEC 60947-1
Complementary
[ie] rated operational current
0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1
0.3 A at 240 V, AC-14, D300 conforming to EN/IEC 60947-5-1
0.6 A at 120 V, AC-14, D300 conforming to EN/IEC 60947-5-1
Product or component type
Complete control station
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1
Colour of base of enclosure
Light grey (RAL 7035)
cable entry
2 knock-outs, clamping capacity: 16 mm
4 knock-outs for ISO M20
marking
CE
contact operation
Slow-break
Electrical shock protection class
Class II conforming to IEC 60536
Material
ABS (acrylonitrile butadiene-styrene)
Colour of cover
Yellow (RAL 1021)
Control station application
Emergency switching off function
electrical reliability
Λ <= 10exp(-6) at 17 V and 5 mA conforming to IEC 60947-5-4
Ik degree of protection
IK05 conforming to EN 50102
Control station composition
1 mushroom head push-button, red, latching 1 NC
Net weight
0.11 kg
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Product destination
For XB7 Ø 22 mm control and signalling units
Short-circuit protection
4 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP54 conforming to IEC 60529
Range of product
Harmony XALE
ambient air temperature for operation
-25…55 °C
standards
EN/IEC 62208
EN/IEC 60947-5-1
EN/IEC 60947-1
EN/IEC 60947-5-5
protective treatment
TC