Complementary
[ie] rated operational current
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
Product certifications
CSA
UL listed
Product or component type
Complete control station
tightening torque
0.8…1.2 N.m conforming to EN/IEC 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
Colour of base of enclosure
Light grey (RAL 7035)
nema degree of protection
NEMA 13
NEMA 4X
cable entry
2 knock-outs for cable entry, clamping capacity: 14 mm
2 knock-outs for Pg 13 cable gland and ISO M20, clamping capacity: 12 mm
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
Contacts material
Silver alloy (Ag/Ni)
contact operation
Slow-break
Operating travel
1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state)
4.3 mm (total travel)
Material
Polycarbonate
Colour of cover
Dark grey (RAL 7016)
Control station application
Start-Stop function
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA conforming to EN/IEC 60947-5-4
Ik degree of protection
IK03 conforming to EN 50102
Control station composition
1 flush push-button, green 1 NO START marking
1 flush push-button, red 1 NC STOP marking
Net weight
0.233 kg
mechanical durability
5000000 cycles
electrical durability
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
Positive opening
With conforming to EN/IEC 60947-5-1 appendix K
Resistance to high pressure washer
7000000 Pa at 55 °C, distance : 0.1 m
Operating force
3.5 N NC changing electrical state
3.8 N NO changing electrical state
Operator profile
2 flush push-buttons
Operators description
Green ''START'' 1 NO - red ''STOP'' 1 NC
Product destination
For XB5 Ø 22 mm control and signalling units
Shock resistance
30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27
Shape of screw head
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver
Short-circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1