XACS412 - Contact block, Harmony XAC, single contact, spring return, front mounting, 40mm horizontal/30mmVertical fixing centres, 1NC - Schneider Electric - Contact block, Harmony XAC, single contact, spring return, front mounting, 40mm horizontal/30mmVertical fixing centres, 1NC - Schneider Electric - 0
XACS412 - Contact block, Harmony XAC, single contact, spring return, front mounting, 40mm horizontal/30mmVertical fixing centres, 1NC - Schneider Electric
12,86 €
12,86 € incl. VAT
Text About:
Contact block, Harmony XAC, single contact, spring return, front mounting, 40mm horizontal/30mmVertical fixing centres, 1NC - Schneider Electric
12,86 €
SPECIFICATIONS
Main
[ithe] thermal current under enclosure 10 A
[ui] rated insulation voltage 500 V (pollution degree 3) conforming to IEC 60947-1
component name XACS
contact block type Single
Complementary
product compatibility XACA
ZA2B... head
Product or component type Contact block
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-1
Connections - terminals Screw clamp terminals, 1 x 2.5 mm² with or without cable end
Screw clamp terminals, 2 x 1.5 mm² with or without cable end
contact operation Slow-break
Contacts type and composition 1 NC
rated operational power in w 42 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
45 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
60 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Horizontal fixing centres 40 mm
Type of operator Spring return
Electrical circuit type Control circuit
rated operational power in va 140 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 24 V 50/60 Hz, load factor = 0.5 (inductive load)
385 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 48 V 50/60 Hz, load factor = 0.5 (inductive load)
455 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 230 V 50/60 Hz, load factor = 0.5 (inductive load)
525 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 127 V 50/60 Hz, load factor = 0.5 (inductive load)
contact code designation A300 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A
Q300 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
Mounting of block Front mounting
Net weight 0.07 kg
mechanical durability 1000000 cycles
Vertical fixing centres 30 mm
Maximum resistance across terminals 25 MOhm
Mechanical interlocking Without mechanical interlock
Shock resistance 100 gn conforming to IEC 60068-2-27
Terminal identifier (13-14)NON !@ !(11-12)NC
Short-circuit protection 10 A fuse protection by cartridge fuse type gG
Terminals description iso n°1 (11-12)NC
Environment
Ambient air temp for storage/transportation -40…70 °C
Range of product Harmony XAC
ambient air temperature for operation -25…70 °C
standards EN 60947-5-1
CSA C22.2 No 14
IEC 60947-5-1
vibration resistance 15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6