Complementary
product compatibility
ZA2B... head
XACA
Product or component type
Contact block
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
Connections - terminals
Screw clamp terminals, 1 x 2.5 mm² with or without cable end
Screw clamp terminals, 2 x 1.5 mm² with or without cable end
contact operation
Slow-break
Contacts type and composition
1 NO
rated operational power in w
42 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
45 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
60 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Horizontal fixing centres
40 mm
Type of operator
Spring return
Electrical circuit type
Control circuit
rated operational power in va
140 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 24 V 50/60 Hz, load factor = 0.5 (inductive load)
385 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 48 V 50/60 Hz, load factor = 0.5 (inductive load)
455 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 230 V 50/60 Hz, load factor = 0.5 (inductive load)
525 VA AC-15 for 1000000 cycles, operating rate <60 cyc/mn at 127 V 50/60 Hz, load factor = 0.5 (inductive load)
contact code designation
A300 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A
Q300 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
Mounting of block
Front mounting
Net weight
0.07 kg
mechanical durability
1000000 cycles
Vertical fixing centres
30 mm
Maximum resistance across terminals
25 MOhm
Mechanical interlocking
Without mechanical interlock
Shock resistance
100 gn conforming to IEC 60068-2-27
Terminal identifier
(13-14)NON !@ !(11-12)NC
Short-circuit protection
10 A fuse protection by cartridge fuse type gG
Terminals description iso n°1
(13-14)NON
Environment
Ambient air temp for storage/transportation
-40…70 °C
Range of product
Harmony XAC
ambient air temperature for operation
-25…70 °C
standards
CSA C22.2 No 14
EN 60947-5-1
IEC 60947-5-1
vibration resistance