Main
Device short name
XACA
[ithe] thermal current under enclosure
10 A
Complementary
Control station colour
Yellow
Product or component type
Pendant control station
Control station type
Double insulated
Connections - terminals
Screw clamp terminals, 1 x 2.5 mm² with or without cable end
Screw clamp terminals, 2 x 1.5 mm² with or without cable end
Enclosure material
Polypropylene
rated operational power in w
40 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
48 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
65 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Ik degree of protection
IK08 conforming to EN 50102
contact code designation
A600 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A
A600 AC-15, Ue = 600 V, Ie = 1.2 A conforming to IEC 60947-5-1 appendix A
Q600 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A
Q600 DC-13, Ue = 600 V, Ie = 0.1 A conforming to IEC 60947-5-1 appendix A
mechanical durability
1000000 cycles
Shock resistance
100 gn conforming to IEC 60068-2-27
Short-circuit protection
10 A fuse protection by cartridge fuse type gG
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP65 conforming to IEC 60529
Range of product
Harmony XAC
ambient air temperature for operation
-25…70 °C
overvoltage category
Class II conforming to IEC 61140
vibration resistance
15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
protective treatment
TH