Complementary
product compatibility
Variable speed drive ATV630 wall mount, motor: 3 kW, 380...480 V
Variable speed drive ATV630 wall mount, motor: 4 kW, 380...480 V
Variable speed drive ATV630 wall mount, motor: 5.5 kW, 380...480 V
Variable speed drive ATV630 wall mount, motor: 1.5 kW, 200...240 V
Variable speed drive ATV630 wall mount, motor: 2.2 kW, 200...240 V
Variable speed drive ATV630 wall mount, motor: 3 kW, 200...240 V
Variable speed drive ATV650 wall mount, motor: 3 kW, 380...480 V
Variable speed drive ATV650 wall mount, motor: 4 kW, 380...480 V
Variable speed drive ATV650 wall mount, motor: 5.5 kW, 380...480 V
Variable speed drive ATV930 wall mount, motor: 3 kW, 380...480 V
Variable speed drive ATV930 wall mount, motor: 4 kW, 380...480 V
Variable speed drive ATV930 wall mount, motor: 5.5 kW, 380...480 V
Variable speed drive ATV930 wall mount, motor: 1.5 kW, 200...240 V
Variable speed drive ATV930 wall mount, motor: 2.2 kW, 200...240 V
Variable speed drive ATV930 wall mount, motor: 3 kW, 200...240 V
Variable speed drive ATV950 wall mount, motor: 3 kW, 380...480 V
Variable speed drive ATV950 wall mount, motor: 4 kW, 380...480 V
Variable speed drive ATV950 wall mount, motor: 5.5 kW, 380...480 V
[in] rated current
15 A
range compatibility
Altivar Process ATV900
Altivar Process ATV600
Handle front plate colour
455 mm
maximum motor cable length
1000 m unshielded cable
500 m shielded cable
Product or component type
Sinus filter
thermal losses
76 W at 4 kHz
Max current
1.20 x nominal current (duration = 60 s)
width (w)
220 mm
mechanical robustness
Shocks class 3M4 conforming to IEC 60721-3-3
Vibrations class 3M4 conforming to IEC 60721-3-3
switching frequency
4...8 kHz
Net weight
13.5 kg
Maximum voltage drop at rated load
8 %
Permissible voltage
480 V AC
depth
210 mm
Pollution degree
2 conforming to IEC 61800-5-1
electrical connection
terminal block, connection capacity: 6 mm² / AWG 10
maximum output frequency
100 Hz
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP20
IP21 (with kit VW3A53901)
operating altitude
<= 1000 m without current derating
1000...4000 m with current derating 1 % per 100 m
ambient air temperature for operation
50…60 °C (with current derating 1.5 % per °C)
-15…50 °C (without current derating)
Environmental characteristics
Biological pollution resistance class 3B1 conforming to IEC 60721-3-3
Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3
Dust pollution resistance class 3S3 conforming to IEC 60721-3-3
relative humidity
5…95 % without condensation